RS6200006r61January 2015This manual is to be used by qualified, professionally trained HVAC technicians only. Goodmandoes not assume any responsibilit
PRODUCT IDENTIFICATION10Model # DescriptionVSZ13**1AAValue Split Z heat pump, 13 Seer R410A heat pump units. Introduces Value Line 13 SEER heat pump
SERVICING100S-11 CHECKING LOSS OF CHARGE PROTEC-TOR(Heat Pump Models)The loss of charge protectors senses the pressure in theliquid line and will open
SERVICING101OHMMETERCAPACITORTESTING CAPACITOR RESISTANCE2. Set an ohmmeter on its highest ohm scale and connectthe leads to the capacitor -A. Good C
SERVICING102S-16A CHECKING FAN AND BLOWER MOTORWINDINGS (PSC MOTORS)The auto reset fan motor overload is designed to protect themotor against high tem
SERVICING103- Connectors are oriented "down" (or as recommended by equipment manufacturer). - Arrange harnesses with "drip loop" u
SERVICING104- Connectors are oriented "down" (or as recommended by equipment manufacturer). - Arrange harnesses with "drip loop" u
SERVICING105S-16C CHECKING ECM MOTOR WINDINGSHIGH VOLTAGE!Disconnect ALL power before servicingor installing. Multiple power sourcesmay be present. Fa
SERVICING106Model Switch 5 Switch 6 CFMOFFOFF1,200ONOFF1,000OFFON800ONON600OFFOFF1,600ONOFF1,400OFFON1,200ONON1,000OFFOFF2,000ON OFF1,800OFF ON1,600ON
SERVICING107S-16E BLOWER PERFORMANCE DATASPEED STATICMBR800**-*SCFMMBR1200**-*SCFMMBR1600**-*SCFMMBR2000**-*SCFM0.1 1,240 1,500 1,800 2,1600.2 1,170 1
SERVICING108S-16G CHECKING EMERSON ULTRATECHTM ECMMOTORSDESCRIPTIONThe AVPTC and MBVC models utilize an Emerson, 4-wirevariable speed ECM blower motor
SERVICING10911. Reconnect the 4-wire harness from control board tomotor.Electrical Checks - High Voltage Power CircuitsHIGH VOLTAGE!Disconnect ALL pow
PRODUCT IDENTIFICATION11Model # DescriptionGSX130**1AAGoodman Split X Condenser 13 Seer condensing units. Introduction of Goodman 13 SEER R-410A Cond
SERVICING1107. Locate the 3-circuit connector in the control/end bell.Using an ohmmeter, check the resistance between eachterminal in the connector.
SERVICING111Dehumidification Disable/Enable Dipswitch - Reducescooling airflow by ~ 15% when enabled AND when used witha humidistat (such as DEHUM1).
SERVICING112NOTE: When 8kW and 10kW heat kits are used with anAVPTC1830 and AVPTC313, matched with 2-ton outdoorunit, see Note 1below.1 Set Heater Ki
SERVICING113CIRCULATOR BLOWERThis air handler is equipped with a multi-speed circulatorblower. This blower provides ease in adjusting blowerspeeds.
SERVICING1144. Locate the blower speed selection DIP switches on theintegrated control module. Select the desired “cooling”speed tap by positioning s
SERVICING115• Profile A provides only an OFF delay of one (1) minuteat 100% of the cooling demand airflow.OFF100% CFM 100% CFM1 minOFF• Profile B ramp
SERVICING116NOTE: Airflow blink codes are approximations of actual airflow. Airflowsprovided are at 0.3 static. B -------
SERVICING117NOTE: Airflow data shown applies to the electric heat only in either legacy mode or communicating mode operation.* Within thermostat user
SERVICING118TROUBLESHOOTINGELECTROSTATIC DISCHARGE (ESD) PRECATIONSNOTE: Discharge body's static electricity before touchingunit. An electrstaic
SERVICING119COMMUNICATIONS TROUBLESHOOTING CHARTLED LED Status Indication Possible Causes Corrective Action(s) Notes & Cautions Off x Normal co
PRODUCT IDENTIFICATION12Model # DescriptionGSX130301BCGoodman Split X Condenser 13 Seer condensing units. 13 SEER R-410A Condensers: changing from th
SERVICING120DIAGNOSTIC CODES for PCBJA103 Board0140A00070-A7 SEGMENT LED (characters will alternate)DESCRIPTION OF CONDITION(no display) INTERNAL CONT
SERVICING121
SERVICING122
SERVICING123
SERVICING124
SERVICING125S-17 CHECKING COMPRESSORWARNINGHermetic compressor electrical terminal venting canbe dangerous. When insulating material whichsupports a h
SERVICING1263. If a ground is indicated, then carefully remove thecompressor terminal protective cover and inspect forloose leads or insulation breaks
SERVICING1274. With power ON, close the switch.WARNINGLine Voltage now present.A. If the compressor starts and continues to run, the causefor failure
SERVICING1283. Set thermostat to call for heating. System should go intodefrost within 21 seconds.4. Immediately remove jumper from test pins.5. Using
SERVICING129During a cooling or heat pump heating demand, 24Vac issupplied to terminal “G” of the EBTDR to turn on the blowermotor. The EBTDR initiat
PRODUCT IDENTIFICATION13Model # DescriptionSSX140**1AASpecial High Feature Split X Condenser 14 Seer condensing units. Initial release of Goodman 14
SERVICING1303. Provide a thermostat demand for low stage auxiliary heat(W1). Measure the voltage between circuits 1 and 3 atthe on-board electric hea
SERVICING131LED LED Status IndicationPossible CausesCorrective Action(s)Notes & CautionsOff • Norm al condition• No ne • N on e • N one•
SERVICING132SEQUENCE OF OPERATIONThis document covers the basic sequence of operation for atypical application with a mercury bulb thermostat. When a
SERVICING133the “W3” demand is satisfied, the room thermostat willremove the 24Vac from HR2. The contacts on HR2 will openbetween 30 to 70 seconds an
SERVICING134time, if the heater assembly contains a second heaterelement, HR1 will contain a second set of contacts, M3and M4, which will close and tu
SERVICING1354.4 As the temperature indoors increase, it will reach a pointwhere the second stage heat demand, “W2”, is satisfied.When this happens, th
SERVICING136“Y1”. The MBE/AEPF removes the 24Vac from “Ylow/Y1’ at the condenser and the compressor and condenserfan are turned off. The blower moto
SERVICING137VSTB will turn on the blower motor and the motor willramp up to 60% of the speed programmed in the motorbased on the settings of dip switc
SERVICING138SEQUENCE OF OPERATIONAVPTC/MBVC with Single Stage Condensers (24VACLegacy Wired Systems)1.0 Cooling Operation1.1 On a demand for single st
SERVICING1392.5 Upon receiving a demand for auxiliary heat, the controldetermines the appropriate airflow demand for heatpump + auxiliary heat operati
PRODUCT IDENTIFICATION14Model # DescriptionDSX160**1AADeluxe Split X Condenser 16 Seer condensing units. Introduces Goodman 2-stage, 16 SEER condensi
SERVICING1402.5 Upon receiving the high stage auxiliary heat demand, thecontrol operates the ECM blower motor at the high stageauxiliary heat airflow.
SERVICING1413.2 Removing the thermostat demand for continuous fanopens the "G" contacts, removing 24VAC from theintegrated air handler contr
SERVICING142AVPTC/MBVC with ASZC/DSZC Heat Pump and CTK0*Communicating ThemostatThe AVPTC or MBVC air handle/modular blower matchedwith an ASZC or DSZ
SERVICING143 The air handler/modular blower is commanded to endauxiliary heat operation. The air handler control de-energizes the electric heat s
SERVICING144HIGH VOLTAGE!Disconnect ALL power before servicingor installing. Multiple power sourcesmay be present. Failure to do so maycause property
SERVICING145HIGH VOLTAGE!Disconnect ALL power before servicingor installing. Multiple power sourcesmay be present. Failure to do so maycause property
SERVICING146S-101 LEAK TESTING (NITROGEN OR NITRO-GEN-TRACED)To avoid the risk of fire or explosion, never useoxygen, high pressure air or flammable g
SERVICING1477. Close valve to thermocouple vacuum gauge and vacuumpump. Shut off pump and prepare to charge.S-103 CHARGINGWARNINGREFRIGERANT UNDER PR
SERVICING148PISTON KIT CHART(*) SIGNIFIES UNIT REVISION.(1) CORRECT PISTON IS SUPPLIED WITH THE OUTDOOR UNIT.(2) CORRECT PISTON IS SUPPLIED IN THE HIG
SERVICING149IT IS ESSENTIAL THAT INDOOR AND OUTDOOR UNITS BE PROPERLY MATCHED. FAILURE TO FOLLOW THESE INSTRUCTIONS OR TO PROPERLY MATCH EVAPORATORS A
PRODUCT IDENTIFICATION15Model # DescriptionVSX130[18-48]1AAValue Split X condensing units, 13 Seer R410A condensing units. Introduces Value Line 13 S
SERVICING150IT IS ESSENTIAL THAT INDOOR AND OUTDOOR UNITS BE PROPERLY MATCHED. FAILURE TO FOLLOW THESE INSTRUCTIONS OR TO PROPERLY MATCH EVAPORATORS A
SERVICING151IT IS ESSENTIAL THAT INDOOR AND OUTDOOR UNITS BE PROPERLY MATCHED. FAILURE TO FOLLOW THESE INSTRUCTIONS OR TO PROPERLY MATCH EVAPORATORS A
SERVICING152IT IS ESSENTIAL THAT INDOOR AND OUTDOOR UNITS BE PROPERLY MATCHED. FAILURE TO FOLLOW THESE INSTRUCTIONS OR TO PROPERLY MATCH EVAPORATORS A
SERVICING153(*) SIGNIFIES UNIT REVISION.(1) CORRECT PISTON IS SUPPLIED WITH THE OUTDOOR UNIT.(2) CORRECT PISTON IS SUPPLIED IN THE HIGHEST SALES VOLUM
SERVICING154(*) SIGNIFIES UNIT REVISION.(1) CORRECT PISTON IS SUPPLIED WITH THE OUTDOOR UNIT.(2) CORRECT PISTON IS SUPPLIED IN THE HIGHEST SALES VOLUM
SERVICING155S-105B THERMOSTATIC EXPANSION VALVEThe expansion valve is designed to control the rate of liquidrefrigerant flow into an evaporator coil i
SERVICING156PSIG °FPSIG °FPSIG °FPSIG °FPSIG °FPSIG °F12-37.7114.037.8216.074.3318.0100.2420.0120.7522.0137.614-34.7116.038.7218.074.9
SERVICING157LIQUID PRESSURE AT SERVICE VALVE (PSIG)8 1012141618189 585654525048195 60 58 56 54 52 50202 62 60 58 56 54 52208 64 62 60 58 56 54215 66 6
SERVICING158To obtain the degrees temperature of superheat, subtract50.0 from 61.0°F.The difference is 11° Superheat. The 11° Superheat would fallin
SERVICING159NOTE: An optional method is to locate the thermometer atthe suction line service valve. Ensure the thermometermakes adequate contact and i
PRODUCT IDENTIFICATION16Model # DescriptionVSX140[18-19]1AAVSX140[24-25]1AAVSX140[30-31]1AAVSX140[36-37]1AAVSX140[42, 48, 60]1AAValue Split X condens
SERVICING160There are other causes for high head pressure which may befound in the "Service Problem Analysis Guide."If other causes check ou
SERVICING161LONG LINE SET APPLICATION R-410AThis long line set application guideline applies to all AHRI listed R-410A air conditioner and heat pump s
SERVICING162Liquid LineSuction LineWrapped in Armaflex®MetalSleeveHangerWallStudLiquid LineStrapped toSuction LineFigure 1-1.Installation of Refrigera
SERVICING163Floor Joist or Roof RafterAfter the suction line has been strapped to the joist or rafter at 8’ intervals,strap the liquid line to the suc
SERVICING164SECTION 3. OUTDOOR UNIT IS ABOVE THE INDOOR UNITAccessory Air Conditioner (AC) Heat Pump (HP)Crankcase Heater (40 watts minimum) Yes YesH
SERVICING165 3. An inverted suction line trap must be installed on the suction line just before the inlet to the indoor unit (see Figure4-1). The top
SERVICING166 3. Table 5-2 lists multiplier values to recalculate system cooling capacity as a function of a system’s equivalent linelength (as calcul
SERVICING167Additional Refrigerant(oz. per lineal foot)3/8” liquid only 0.603/8” liquid and 5/8” suction 0.633/8” liquid and 3/4" suction 0.673/8
SERVICING168TOTAL EXTERNAL STATICNOTE: Both readings may be taken simultaneously and readdirectly on the manometer if so desired.4. Consult proper tab
ACCESSORIES WIRING DIAGRAMS169HIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL
PRODUCT IDENTIFICATION17Model # DescriptionASX130**1AAAmana® Brand Split X Condenser 13 Seer condensing units. Initial release new models of Amana® B
170ACCESSORIES WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL
ACCESSORIES WIRING DIAGRAMS171HIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL
172ACCESSORIES WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL
ACCESSORIES WIRING DIAGRAMS173HIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL
174ACCESSORIES WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL
ACCESSORIES WIRING DIAGRAMS175HIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL
176ACCESSORIES WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL
ACCESSORIES WIRING DIAGRAMS177HIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL
178ACCESSORIES WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL
ACCESSORIES WIRING DIAGRAMS179HIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL
PRODUCT IDENTIFICATION18Model # DescriptionASX160**1ABAmana® Brand Split X Condenser 16 Seer condensing units. New revisions have screw locations mov
180WIRING DIAGRAMSAIRHANDLERS
181WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
182WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
183WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
184WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
185WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
186WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
187WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
188WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
189WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
PRODUCT IDENTIFICATION19Model # DescriptionACNF****1AAA Single Piece Air Handler Ceiling Mount N Uncased Flowrater. Revision release all models of 13
190WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
191WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
192WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
193WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
194WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
195WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
196WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
197WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
198WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
199WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
Pride and workmanship go into every product to provide our customers with quality products. It is possible, however, thatduring its lifetime a produc
PRODUCT IDENTIFICATION20Model # DescriptionARUF172916AAA24-00-2RCAA Single Piece R Multi-Position PSC Motor Unpainted Flowrater Introduction of new
200WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
201WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
202WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
203WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
204WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
205WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
206WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
207WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
208WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
209WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
PRODUCT IDENTIFICATION21Model # DescriptionASPF****16AAA Single Piece S Multi-Position EEM motor Painted Flowrator. Introduces new ASPF Air HandlersA
210WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
211WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
212WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
213WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
214WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
215WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
216WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
217WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
218WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
219WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
PRODUCT IDENTIFICATION22Model # DescriptionAVPTC183014AAAVPTC313714AAAVPTC426014AAA Single Piece V Multi-Position Variable-Speed Painted T TXV Flowra
220WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
221WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
222WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
223WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
224WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
225WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
226WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
227WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
228WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
229WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
PRODUCT IDENTIFICATION23Model # DescriptionAW UF****16AAA Single Piece Air Handler Wall Mount Unpainted Flowrator. Introduces 13 SEER Dayton wall mo
230WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
231WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
232WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
233WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
234WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
235WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
236WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
237WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
238WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
239WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
PRODUCT IDENTIFICATION24Model # DescriptionMBR****AA-1AA Modular Blower R Multi-Position PSC Motor. Introduces module blower with PSC blower motor.
240WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
241WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
242WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
243WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
244WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
245WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
246WIRING DIAGRAMSWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.DSX180[36-60]1A*USE N.E.C
247WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
248WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
249WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
PRODUCT IDENTIFICATION25Model # DescriptionCAUF*****6AAC Indoor Coil A Upflow/Downflow Uncased Flowrator. Introduces CAUF Dayton Upflow/Downflow coil
250WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
251WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
252WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
253WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
254WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
255WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
256WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
257WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
258WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
259WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
PRODUCT IDENTIFICATION26Model # DescriptionCSCF*****6AAC Indoor Coil S Horizontal Slab Coil C Upainted Flowrator. Release 13 SEER CSCF slab horizont
260WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
261WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
262WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
263WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
264WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
265WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
266WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
267WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
268WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
269WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
PRODUCT IDENTIFICATION27SSZ14361AAPRODUCTTYPE:X: Condenser R-410AZ: Heat Pump R-410APRODUCTFAMILY:S: Split SystemSEER:SEER RatingBRAND:G: Goodman®(St
270WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
271WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
272WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
273WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
274WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
275WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
276WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
277WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
278WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
279WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
PRODUCT IDENTIFICATION28ComfortNet™A S X C 16 024 1 A A PRODUCT TYPE: C: Condenser R-22 H: Heat Pump R-22 X: Condenser R-410A Z: Heat Pump R-410A
280WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
281WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
282WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
283WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
284WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
285WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
286WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
287WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
288WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
289WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
PRODUCT IDENTIFICATION29C A P T 3131 B 4 APRODUCTTYPE: C: Indoor Coil CABINET FINISH: P: Painted EXPANSION DEVICE: T: Factory installed n
290WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
291WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
292WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
293WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
294WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
295WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
296WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
297WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
298WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
299WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
SAFE REFRIGERANT HANDLINGWhile these items will not cover every conceivable situation, they should serve as a useful guide.IMPORTANT INFORMATIONThe su
PRODUCT IDENTIFICATION30MB R 8 00 A A 1DESIGN SERIES: MB: Modular Blower MOTOR TYPE: R: Constant Speed E: Variable Speed AIRFLOW DELIVERED 08
300WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
301WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
302WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
303WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
304WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
305WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
306WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
307WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
308WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
309WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
PRODUCT IDENTIFICATION31All Airhandlers use DIRECT DRIVE MOTORS. Power supply is AC 208-240v, 60 hz, 1 phase.A W U F 3642 1 6 A APRODUCTTYPE:A: Air Ha
310WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
311WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO
PRODUCT IDENTIFICATION32ARUF**14** / ARPT**14**/ASPT**14**Airhandlers use DIRECT DRIVE MOTORS. Power supply is AC 208-230v, 60 hz, 1 phase.ARUF18B14AA
PRODUCT IDENTIFICATION33All Airhandlers use DIRECT DRIVE MOTORS. Power supply is AC 208-230v, 60 hz, 1 phase.ComfortNet™AV P T C 18B 14AA123456,789101
PRODUCT IDENTIFICATION34LIGHT COMMERCIALModel # DescriptionGSX11090*AAGSX11120*AAGoodman Split X Condenser 11 Seer condensing units. Introduction of
PRODUCT IDENTIFICATION35AR Nominal Cooling CapacityModel SeriesAR0904 - 90,000 Btuh (7 1/2 Tons)1204 - 120,000 Btuh (10 Tons)LIGHT COMMERCIALGSX110903
ACCESSORIES36LIGHT COMMERCIALGSX11GSZ11NOTES:• AR Series Air Handlers do not have factory installed electric heat. Purchased as an accessory, these ar
37ACCESSORIES1Contains 20 brackets; fourbrackets needed to anchor unitto pad2Installed on indoor coil.3Field-installed, non-bleed, ex-pansion valve ki
ACCESSORIES38ASX14Model DescriptionASX14018ASX14024ASX14030ASX14036ASX14042ASX14048ASX14060ABK-201Anchor Bracket Kit XXXXXXXASC01Anti-Short Cycle Kit
39ACCESSORIESSSX16Model DescriptionSSX16024*SSX16030*SSX16036*SSX16042*SSX16048*SSX16060*ABK-201Anchor Bracket Kit XXXXXXASC01 Anti-Short Cycle KitXXX
PRODUCT IDENTIFICATION4Model # DescriptionASZ130**1AAAmana® Brand Split Z R410A heat pump 13 Seer heat pump units. Initial release of Amana® Brand 13
ACCESSORIES40ASX/DSX18Model DescriptionA/DSX18036*A/DSX18048*/DSX18060*ABK-201Anchor Bracket Kit X X XASC01 Anti-Short Cycle KitXXXCSR-U-1 Hard-start
41ACCESSORIESComfortNet™Model DescriptionASXC16024DSXC16024ASXC16036DSXC16036ASXC16048DSXC16048ASXC16060DSXC16060ASXC18036DSXC18036ASXC18048DSXC18048A
ACCESSORIES421Contains 20 brackets; four bracketsneeded to anchor unit to pad2Installed on indoor coil.3Required for heat pump applicationswhere ambie
43ACCESSORIESSSZ14Model DescriptionSSZ14018*SSZ14024*SSZ14030*SSZ14036*SSZ14038*SSZ14042*SSZ14048*SSZ14060*AFE18-60AAll-Fuel Kit XXXXXXX XCSR-U-1 Hard
ACCESSORIES44ASZ16/DSZ16Model DescriptionA/DSZ16024*A/DSZ16030*A/DSZ16036*A/DSZ16042*A/DSZ16048*A/DSZ16060*AFE18-60A All-Fuel Kit X X X X X XCSR-U-1 H
45ACCESSORIESASZ/DSZ18Model DescriptionA/DSZ18036*A/DSZ18048*A/DSZ18060*AFE18-60A All-Fuel Kit X X XCSR-U-1 Hard-start Kit XCSR-U-2 Hard-start Kit XCS
ACCESSORIES46ComfortNet™Model DescriptionASZC16024DSZC16024ASZC16036DSZC16036ASZC16048DSZC16048ASZC16060DSZC16060ASZC18036DSZC18036ASZC18048DSZC18048A
47ACCESSORIES SUCTION LINE BULB 1/4 FLARE CONNECTION EXPANSION VALVE EVAPORATOR COIL REMOVE BEFORE INSTALLING EXPANSION VALVESEAL SUPPLIED W/ KITSEA
ACCESSORIES48FSK01AFREEZE THERMOSTATKITT2 T1L2L1BLACK 1THERMOSTATWIRESHORT CYCLEPROTECTORYELLOW 1BLACK 1Y1Y2R1R2YCUNITTERMINALBOARDCONTACTORASC01AANTI
49ACCESSORIESCOIL ACCESSORIESCOIL MODELTX2N4ATXV KITTX 3N4TXV KITTX5N4TXV KITFSK01A FREEZE PROTECTION KITCA*F18246* XXCA*F30306* XXCA*F31316*CA*F3636
PRODUCT IDENTIFICATION5Model # DescriptionASZ160**1AAAmana® Brand Split Z R410A heat pump 16 Seer heat pump units. Initial release of Amana® Brand 16
ACCESSORIES50ELECTRIC HEAT KIT APPLICATIONS - ARUFELECTRIC HEAT KIT APPLICATIONS - ARPFARUF1729 1/16ARUF1824 1/16ARUF1931 1/16ARUF3030 1/16ARUF3642
51ACCESSORIESELECTRIC HEAT KIT APPLICATIONS - AVPTC* Revision level that may or may not be designated.C Circuit breaker option.ELECTRIC HEAT KIT APP
ACCESSORIES52ELECTRIC HEAT KIT APPLICATIONS - ASPFDRAIN PAN INSULATION KITS - ARUF**14**, ARPT**14**, ASPT**14** & ASUF**14**DFK-BDownflow KitD
53ACCESSORIESARPT**14**Heat Kit ApplicationsType / model 18B14-A* 24B14-A* 30B14-A* 36C14-A* 36D14-A* 42D14-A* 48D14-A* 60D14-A*HKSX03XC* XXXXXXXXHKSX
ACCESSORIES54ARUF**14**3 5 6 8 101519202518 715 715 715 715 95024 715 715 715 715 95030B 715 715 715 715 875 87530C 1170 1170 1170 1170 1345 134536 11
55ACCESSORIESASUF**14**3 5 6 8 10 15 19 20 2529 71 5 715 715 7 15 87539 1170 11 70 1170 1 17 0 134 5 134549 1170 11 70 1170 1 17 0 134 5 134559 1590 1
ACCESSORIES56ASPT**14**3 5 6 8 10 15 19 20 25ASPT24B14715 715 715 715 875 NR NR NR NRASPT30C14730 715 715 715 950 NR NR NR NRASPT36C14NR 1170 1170 117
57ACCESSORIES3 5 6 8 10 15 19 20 21 or 25AVPTC24B14 550 650 700 800 850 NR NR NR NRAVPTC30C14 600 700 750 875 950 NR NR NR NRAVPTC36C14 NR 850 900 100
PRODUCT DESIGN58This section gives a basic description of cooling unit opera-tion, its various components and their basic operation.Ensure your system
PRODUCT DESIGN59The ASX & ASXC [16 & 18], ASZ & ASZC [16 & 18], DSX &DSXC [16 & 18] and DSZ & DSZC [16 & 18] series sp
PRODUCT IDENTIFICATION6Model # DescriptionASZC160**1AAAmana® brand Split Z Communicating heat pump, 16 Seer R410A heat pum p units. Introduces Goodma
PRODUCT DESIGN60CAPACITY CONTROL - LEGACY MODELSDuring the compression process, there are several pocketswithin the scroll that are compressing gas. M
SYSTEM OPERATION61COOLINGThe refrigerant used in the system is R-410A. It is a clear,colorless, non-toxic and non-irritating liquid. R-410A is a50:50
SYSTEM OPERATION62When the thermostat is satisfied, appropriate commands aresent to the UC control. The compressor relay and outdoorfan relay is de-
SYSTEM OPERATION63COOLING CYCLEHEATING CYCLEIndoorCoilAccumulatorBi-FlowFilter DryerOutdoorCoilThermostaticExpansionValveCheck ValveReversing Valve(De
SYSTEM OPERATION64RESTRICTOR ORIFICE ASSEMBLYIN COOLING OPERATIONRESTRICTOR ORIFICE ASSEMBLYIN HEATING OPERATIONIn the cooling mode, the orifice is pu
SYSTEM OPERATION65AFE18-60A CONTROL BOARDDESCRIPTIONThe AFE18 control is designed for use in heat pump applica-tions where the indoor coil is located
66TROUBLESHOOTING CHARTCom plaintSystem Operating PressuresPOSSIBLE CAUSEDOTS IN ANALYSISGUIDE INDICATE"POSSIBLE CAUSE"SYMPTOMSystem will no
SERVICING67HIGH VOLTAGE!Disconnect ALL power before servicing or installing. Multiple power sources may be present. Failure todo so may cause property
SERVICING68S-1 CHECKING VOLTAGE1. Remove outer case, control panel cover, etc., from unitbeing tested.With power ON:WARNINGLine Voltage now present.2.
SERVICING69Indoor Blower MotorWith power ON:WARNINGLine Voltage now present.1. Set fan selector switch at thermostat to "ON" position.2. Wit
PRODUCT IDENTIFICATION7Model # Descrip tionDSZ160**1AADeluxe Spl it Z Heat Pum p 16 Seer heat pump units. Introduces Goodman 2-stage 16 SEER heat pu
SERVICING7012RC12RC12RCCTK0*ThermostatCT™ CompatibleModular BlowerIntegrated Control ModuleCT™ Compatible AC/HPIntegrated Control ModuleSystem Wiring
SERVICING71To exit an equipment submenu and revert back to theequipment menus, touch the Menu key. Touch Menu againto revert back to the Thermostat O
SERVICING72Submenu Item Indication (for Display Only; not User Modifiable)Electric Heat Size (HTR KW) Displays the size in kW of the selected electric
SERVICING73Submenu Item User Modifiable Options CommentsOutdoor Air Temperature(AIR TMP)Displays the outdoor air temperatureSensor may or may not be a
SERVICING74Submenu Item Indication (for Display Only; not User Modifiable)Mode (MODE) Displays the current air conditioner operating modeCFM (CFM) Dis
SERVICING75S-5 CHECKING CYCLE PROTECTORSome models feature a solid state, delay-on make after breaktime delay relay installed in the low voltage circu
SERVICING763. Using a voltmeter, test across terminals.A. L2 - T1 - No voltage indicates CC1 contacts open.If a no voltage reading is obtained - repl
SERVICING77Condenser fan control for the ASXC/ASZC and DSXC/DSZCmodels is fully integrated into the UC control. The controlsupports one- or two-speed
SERVICING78 Schematic Abbreviation DescriptionsHTCO High Temperature Cut Out SwitchHPCO High Pressure Cut Out SwitchLPCO Low Pressure Cut Out S
SERVICING79Status LED Status LED Description Status LED Troubleshooting InformationGreen “POWER” Module has power Supply voltage is present at modul
PRODUCT IDENTIFICATION8Model # DescriptionGSZ13**1AA Goodman Split Z R410A Heat Pump 13 Seer heat pump units. Initial release with Regal Beloit moto
SERVICING80DIAGNOSTICS - 2-WIRE MODULEApplies to ASX130[18-60]CA, ASX140[18-36]1CA,ASX140421DA, and ASX140[48-60]1BA unitsComfort Alert™ is self-cont
SERVICING81Status LED Status LED Description Status LED Troubleshooting InformationGreen “POWER” Module has power Supply voltage is present at module
SERVICING82S-10A COPELAND COMFORT ALERTTM -UNITARY (UC) CONTROL DIAGNOSTICSApplies to ASXC, ASZC, DSXC, and DSZC modelsHIGH VOLTAGE!Disconnect ALL pow
SERVICING83Symptoms of Abnormal Operation (Legacy & ComfortNet™ Thermostat) Diagnostic/Status LED Codes Faul t Description Co mf o rt Net™ Thermos
SERVICING84Diagnostic/Status LED Codes ComfortNet™ Thermostat Only Symptoms of Abnormal Operation (Legacy & ComfortNet™ Thermostat) Green Yellow
SERVICING85Diagnostic/Status LED Codes ComfortNet™ Thermostat Only Symptoms of Abnormal Operation (Legacy & ComfortNet™ Thermostat) Green Yellow
SERVICING86Diagnostic/Status LED Codes Com f or tNe t ™ Thermostat Only Symptoms of Abnormal Operation (Legacy & ComfortNet™ Thermostat) Green Ye
SERVICING87Diagnostic/Status LED Codes Com f o r tNet™ Thermostat Only Symptoms of Abnormal Operation (Legacy & ComfortNet™ Thermostat) Green Yel
SERVICING885.)4!29$)!'./34)##/$%33YMPTOMSOF!BNORMAL/PERATION,EGACY#OMFORT.ET4HERMOSTAT$IAGNOSTIC3TATUS,%$$ISPLAY#ODES&AULT
SERVICING895.)4!29$)!'./34)##/$%33YMPTOMSOF!BNORMAL/PERATION,EGACY#OMFORT.ET4HERMOSTAT$IAGNOSTIC3TATUS,%$$ISPLAY#ODES &AULT
PRODUCT IDENTIFICATION9Model # DescriptionSSZ140**1AASpecial High Feature Split Z R410A heat pump 14 Seer heat pump units. Initial release of Goodman
SERVICING905.)4!29$)!'./34)##/$%33YMPTOMSOF!BNORMAL/PERATION,EGACY#OMFORT.ET4HERMOSTAT$IAGNOSTIC3TATUS,%$$ISPLAY#ODES &AULT
SERVICING91Compressor and outdoor f. Low pressure switch trip 3 times within same thermostat demand. Thermostat demand is present. Integrated contr
SERVICING92 Run time for last 4 cycles is less than 3 minutes each.Compressor protector has not tripped.Low pressure and high pressure switches are cl
SERVICING93Compressor and outdoor f .Low pressure and high pressure switches are closed.Open start circuit has been detected 4 times with 5 minute del
SERVICING94Air conditioner/heat pump may appear to be operating normally. Compressor protector may be open (compressor and outdoor f Integrated cont
SERVICING950140M00407-A7 SEGMENT LED (DS2)7 SEGMENT LED (DS1)DESCRIPTION OF CONDITION0 n Standby0 1 Low Pressure CO Trip0 1 Low Side Fault0 2 High
SERVICING96S-10B COPELAND CORESENSE™DIAGNOSTICS - 3-WIRE MODULEApplies to ASX /ASZ and DSX/DSZ unitsThe CoreSense™ module is self-contained with no r
SERVICING97DIAGNOSTICS TABLE: CORESENSE™ MODULEFlash code number corresponds to the number of LED flashes, followed by a pause and then repeated.TRIP
SERVICING98DIAGNOSTICS TABLE: CORESENSE™ MODULE (cont.)Flash code number corresponds to the number of LED flashes, followed by a pause and then repea
SERVICING99 Table 1 - Quick Reference Table