This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman
does not assume any responsibility for property damage or personal injury due to improper
service procedures or services performed by an unqualified person.
Copyright © 2006 - 2015 Goodman Manufacturing Company, L.P.
ANX, SSX, ASX, GSX, DSX, ASXC, DSXC
Condensing Units,
ANZ, SSZ, ASZ, GSZ, DSZ, ASZC, DSZC, VSX, VSZ
Split System Heat Pumps
with R-410A Refrigerant
Blowers, Coils, & Accessories
Service Instructions
Page view 0
1 2 3 4 5 6 ... 310 311

Summary of Contents

Page 1 - Service Instructions

RS6200006r61January 2015This manual is to be used by qualified, professionally trained HVAC technicians only. Goodmandoes not assume any responsibilit

Page 2 - IMPORTANT INFORMATION

PRODUCT IDENTIFICATION10Model # DescriptionVSZ13**1AAValue Split Z heat pump, 13 Seer R410A heat pump units. Introduces Value Line 13 SEER heat pump

Page 3 - SAFE REFRIGERANT HANDLING

SERVICING100S-11 CHECKING LOSS OF CHARGE PROTEC-TOR(Heat Pump Models)The loss of charge protectors senses the pressure in theliquid line and will open

Page 4 - Split System Heat Pumps R410A

SERVICING101OHMMETERCAPACITORTESTING CAPACITOR RESISTANCE2. Set an ohmmeter on its highest ohm scale and connectthe leads to the capacitor -A. Good C

Page 5

SERVICING102S-16A CHECKING FAN AND BLOWER MOTORWINDINGS (PSC MOTORS)The auto reset fan motor overload is designed to protect themotor against high tem

Page 6

SERVICING103- Connectors are oriented "down" (or as recommended by equipment manufacturer). - Arrange harnesses with "drip loop" u

Page 7

SERVICING104- Connectors are oriented "down" (or as recommended by equipment manufacturer). - Arrange harnesses with "drip loop" u

Page 8

SERVICING105S-16C CHECKING ECM MOTOR WINDINGSHIGH VOLTAGE!Disconnect ALL power before servicingor installing. Multiple power sourcesmay be present. Fa

Page 9

SERVICING106Model Switch 5 Switch 6 CFMOFFOFF1,200ONOFF1,000OFFON800ONON600OFFOFF1,600ONOFF1,400OFFON1,200ONON1,000OFFOFF2,000ON OFF1,800OFF ON1,600ON

Page 10 - PRODUCT IDENTIFICATION

SERVICING107S-16E BLOWER PERFORMANCE DATASPEED STATICMBR800**-*SCFMMBR1200**-*SCFMMBR1600**-*SCFMMBR2000**-*SCFM0.1 1,240 1,500 1,800 2,1600.2 1,170 1

Page 11

SERVICING108S-16G CHECKING EMERSON ULTRATECHTM ECMMOTORSDESCRIPTIONThe AVPTC and MBVC models utilize an Emerson, 4-wirevariable speed ECM blower motor

Page 12

SERVICING10911. Reconnect the 4-wire harness from control board tomotor.Electrical Checks - High Voltage Power CircuitsHIGH VOLTAGE!Disconnect ALL pow

Page 13

PRODUCT IDENTIFICATION11Model # DescriptionGSX130**1AAGoodman Split X Condenser 13 Seer condensing units. Introduction of Goodman 13 SEER R-410A Cond

Page 14

SERVICING1107. Locate the 3-circuit connector in the control/end bell.Using an ohmmeter, check the resistance between eachterminal in the connector.

Page 15

SERVICING111Dehumidification Disable/Enable Dipswitch - Reducescooling airflow by ~ 15% when enabled AND when used witha humidistat (such as DEHUM1).

Page 16

SERVICING112NOTE: When 8kW and 10kW heat kits are used with anAVPTC1830 and AVPTC313, matched with 2-ton outdoorunit, see Note 1below.1 Set Heater Ki

Page 17

SERVICING113CIRCULATOR BLOWERThis air handler is equipped with a multi-speed circulatorblower. This blower provides ease in adjusting blowerspeeds.

Page 18

SERVICING1144. Locate the blower speed selection DIP switches on theintegrated control module. Select the desired “cooling”speed tap by positioning s

Page 19

SERVICING115• Profile A provides only an OFF delay of one (1) minuteat 100% of the cooling demand airflow.OFF100% CFM 100% CFM1 minOFF• Profile B ramp

Page 20

SERVICING116NOTE: Airflow blink codes are approximations of actual airflow. Airflowsprovided are at 0.3 static. B -------

Page 21

SERVICING117NOTE: Airflow data shown applies to the electric heat only in either legacy mode or communicating mode operation.* Within thermostat user

Page 22

SERVICING118TROUBLESHOOTINGELECTROSTATIC DISCHARGE (ESD) PRECATIONSNOTE: Discharge body's static electricity before touchingunit. An electrstaic

Page 23

SERVICING119COMMUNICATIONS TROUBLESHOOTING CHARTLED LED Status Indication Possible Causes Corrective Action(s) Notes & Cautions Off x Normal co

Page 24

PRODUCT IDENTIFICATION12Model # DescriptionGSX130301BCGoodman Split X Condenser 13 Seer condensing units. 13 SEER R-410A Condensers: changing from th

Page 25

SERVICING120DIAGNOSTIC CODES for PCBJA103 Board0140A00070-A7 SEGMENT LED (characters will alternate)DESCRIPTION OF CONDITION(no display) INTERNAL CONT

Page 26

SERVICING121

Page 27

SERVICING122

Page 30 - MB V C 12 00 A A 1

SERVICING125S-17 CHECKING COMPRESSORWARNINGHermetic compressor electrical terminal venting canbe dangerous. When insulating material whichsupports a h

Page 31

SERVICING1263. If a ground is indicated, then carefully remove thecompressor terminal protective cover and inspect forloose leads or insulation breaks

Page 32 - ASPT**14**

SERVICING1274. With power ON, close the switch.WARNINGLine Voltage now present.A. If the compressor starts and continues to run, the causefor failure

Page 33 - ComfortNet™

SERVICING1283. Set thermostat to call for heating. System should go intodefrost within 21 seconds.4. Immediately remove jumper from test pins.5. Using

Page 34 - LIGHT COMMERCIAL

SERVICING129During a cooling or heat pump heating demand, 24Vac issupplied to terminal “G” of the EBTDR to turn on the blowermotor. The EBTDR initiat

Page 35 - G S X 11 090 3 A A

PRODUCT IDENTIFICATION13Model # DescriptionSSX140**1AASpecial High Feature Split X Condenser 14 Seer condensing units. Initial release of Goodman 14

Page 36 - ELECTRIC HEATER KITS

SERVICING1303. Provide a thermostat demand for low stage auxiliary heat(W1). Measure the voltage between circuits 1 and 3 atthe on-board electric hea

Page 37 - GSX13 Three-phase models

SERVICING131LED LED Status IndicationPossible CausesCorrective Action(s)Notes & CautionsOff • Norm al condition• No ne • N on e • N one•

Page 38

SERVICING132SEQUENCE OF OPERATIONThis document covers the basic sequence of operation for atypical application with a mercury bulb thermostat. When a

Page 39

SERVICING133the “W3” demand is satisfied, the room thermostat willremove the 24Vac from HR2. The contacts on HR2 will openbetween 30 to 70 seconds an

Page 40

SERVICING134time, if the heater assembly contains a second heaterelement, HR1 will contain a second set of contacts, M3and M4, which will close and tu

Page 41

SERVICING1354.4 As the temperature indoors increase, it will reach a pointwhere the second stage heat demand, “W2”, is satisfied.When this happens, th

Page 42 - GSZ13 Three

SERVICING136“Y1”. The MBE/AEPF removes the 24Vac from “Ylow/Y1’ at the condenser and the compressor and condenserfan are turned off. The blower moto

Page 43

SERVICING137VSTB will turn on the blower motor and the motor willramp up to 60% of the speed programmed in the motorbased on the settings of dip switc

Page 44

SERVICING138SEQUENCE OF OPERATIONAVPTC/MBVC with Single Stage Condensers (24VACLegacy Wired Systems)1.0 Cooling Operation1.1 On a demand for single st

Page 45

SERVICING1392.5 Upon receiving a demand for auxiliary heat, the controldetermines the appropriate airflow demand for heatpump + auxiliary heat operati

Page 46

PRODUCT IDENTIFICATION14Model # DescriptionDSX160**1AADeluxe Split X Condenser 16 Seer condensing units. Introduces Goodman 2-stage, 16 SEER condensi

Page 47

SERVICING1402.5 Upon receiving the high stage auxiliary heat demand, thecontrol operates the ECM blower motor at the high stageauxiliary heat airflow.

Page 48

SERVICING1413.2 Removing the thermostat demand for continuous fanopens the "G" contacts, removing 24VAC from theintegrated air handler contr

Page 49

SERVICING142AVPTC/MBVC with ASZC/DSZC Heat Pump and CTK0*Communicating ThemostatThe AVPTC or MBVC air handle/modular blower matchedwith an ASZC or DSZ

Page 50

SERVICING143 The air handler/modular blower is commanded to endauxiliary heat operation. The air handler control de-energizes the electric heat s

Page 51 - C Circuit Breaker option

SERVICING144HIGH VOLTAGE!Disconnect ALL power before servicingor installing. Multiple power sourcesmay be present. Failure to do so maycause property

Page 52

SERVICING145HIGH VOLTAGE!Disconnect ALL power before servicingor installing. Multiple power sourcesmay be present. Failure to do so maycause property

Page 53

SERVICING146S-101 LEAK TESTING (NITROGEN OR NITRO-GEN-TRACED)To avoid the risk of fire or explosion, never useoxygen, high pressure air or flammable g

Page 54

SERVICING1477. Close valve to thermocouple vacuum gauge and vacuumpump. Shut off pump and prepare to charge.S-103 CHARGINGWARNINGREFRIGERANT UNDER PR

Page 55

SERVICING148PISTON KIT CHART(*) SIGNIFIES UNIT REVISION.(1) CORRECT PISTON IS SUPPLIED WITH THE OUTDOOR UNIT.(2) CORRECT PISTON IS SUPPLIED IN THE HIG

Page 56

SERVICING149IT IS ESSENTIAL THAT INDOOR AND OUTDOOR UNITS BE PROPERLY MATCHED. FAILURE TO FOLLOW THESE INSTRUCTIONS OR TO PROPERLY MATCH EVAPORATORS A

Page 57

PRODUCT IDENTIFICATION15Model # DescriptionVSX130[18-48]1AAValue Split X condensing units, 13 Seer R410A condensing units. Introduces Value Line 13 S

Page 58 - PRODUCT DESIGN

SERVICING150IT IS ESSENTIAL THAT INDOOR AND OUTDOOR UNITS BE PROPERLY MATCHED. FAILURE TO FOLLOW THESE INSTRUCTIONS OR TO PROPERLY MATCH EVAPORATORS A

Page 59

SERVICING151IT IS ESSENTIAL THAT INDOOR AND OUTDOOR UNITS BE PROPERLY MATCHED. FAILURE TO FOLLOW THESE INSTRUCTIONS OR TO PROPERLY MATCH EVAPORATORS A

Page 60

SERVICING152IT IS ESSENTIAL THAT INDOOR AND OUTDOOR UNITS BE PROPERLY MATCHED. FAILURE TO FOLLOW THESE INSTRUCTIONS OR TO PROPERLY MATCH EVAPORATORS A

Page 61 - SYSTEM OPERATION

SERVICING153(*) SIGNIFIES UNIT REVISION.(1) CORRECT PISTON IS SUPPLIED WITH THE OUTDOOR UNIT.(2) CORRECT PISTON IS SUPPLIED IN THE HIGHEST SALES VOLUM

Page 62

SERVICING154(*) SIGNIFIES UNIT REVISION.(1) CORRECT PISTON IS SUPPLIED WITH THE OUTDOOR UNIT.(2) CORRECT PISTON IS SUPPLIED IN THE HIGHEST SALES VOLUM

Page 63

SERVICING155S-105B THERMOSTATIC EXPANSION VALVEThe expansion valve is designed to control the rate of liquidrefrigerant flow into an evaporator coil i

Page 64

SERVICING156PSIG °FPSIG °FPSIG °FPSIG °FPSIG °FPSIG °F12-37.7114.037.8216.074.3318.0100.2420.0120.7522.0137.614-34.7116.038.7218.074.9

Page 65

SERVICING157LIQUID PRESSURE AT SERVICE VALVE (PSIG)8 1012141618189 585654525048195 60 58 56 54 52 50202 62 60 58 56 54 52208 64 62 60 58 56 54215 66 6

Page 66 - TROUBLESHOOTING CHART

SERVICING158To obtain the degrees temperature of superheat, subtract50.0 from 61.0°F.The difference is 11° Superheat. The 11° Superheat would fallin

Page 67

SERVICING159NOTE: An optional method is to locate the thermometer atthe suction line service valve. Ensure the thermometermakes adequate contact and i

Page 68

PRODUCT IDENTIFICATION16Model # DescriptionVSX140[18-19]1AAVSX140[24-25]1AAVSX140[30-31]1AAVSX140[36-37]1AAVSX140[42, 48, 60]1AAValue Split X condens

Page 69

SERVICING160There are other causes for high head pressure which may befound in the "Service Problem Analysis Guide."If other causes check ou

Page 70

SERVICING161LONG LINE SET APPLICATION R-410AThis long line set application guideline applies to all AHRI listed R-410A air conditioner and heat pump s

Page 71

SERVICING162Liquid LineSuction LineWrapped in Armaflex®MetalSleeveHangerWallStudLiquid LineStrapped toSuction LineFigure 1-1.Installation of Refrigera

Page 72

SERVICING163Floor Joist or Roof RafterAfter the suction line has been strapped to the joist or rafter at 8’ intervals,strap the liquid line to the suc

Page 73

SERVICING164SECTION 3. OUTDOOR UNIT IS ABOVE THE INDOOR UNITAccessory Air Conditioner (AC) Heat Pump (HP)Crankcase Heater (40 watts minimum) Yes YesH

Page 74

SERVICING165 3. An inverted suction line trap must be installed on the suction line just before the inlet to the indoor unit (see Figure4-1). The top

Page 75

SERVICING166 3. Table 5-2 lists multiplier values to recalculate system cooling capacity as a function of a system’s equivalent linelength (as calcul

Page 76

SERVICING167Additional Refrigerant(oz. per lineal foot)3/8” liquid only 0.603/8” liquid and 5/8” suction 0.633/8” liquid and 3/4" suction 0.673/8

Page 77

SERVICING168TOTAL EXTERNAL STATICNOTE: Both readings may be taken simultaneously and readdirectly on the manometer if so desired.4. Consult proper tab

Page 78

ACCESSORIES WIRING DIAGRAMS169HIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL

Page 79

PRODUCT IDENTIFICATION17Model # DescriptionASX130**1AAAmana® Brand Split X Condenser 13 Seer condensing units. Initial release new models of Amana® B

Page 80

170ACCESSORIES WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL

Page 81

ACCESSORIES WIRING DIAGRAMS171HIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL

Page 82

172ACCESSORIES WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL

Page 83

ACCESSORIES WIRING DIAGRAMS173HIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL

Page 84

174ACCESSORIES WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL

Page 85

ACCESSORIES WIRING DIAGRAMS175HIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL

Page 86

176ACCESSORIES WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL

Page 87

ACCESSORIES WIRING DIAGRAMS177HIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL

Page 88 - PCBHR104

178ACCESSORIES WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL

Page 89

ACCESSORIES WIRING DIAGRAMS179HIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAIL

Page 90

PRODUCT IDENTIFICATION18Model # DescriptionASX160**1ABAmana® Brand Split X Condenser 16 Seer condensing units. New revisions have screw locations mov

Page 91

180WIRING DIAGRAMSAIRHANDLERS

Page 92

181WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 93

182WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 94

183WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 95

184WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 96

185WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 97

186WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 98

187WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 99

188WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 100 - SERVICING

189WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 101

PRODUCT IDENTIFICATION19Model # DescriptionACNF****1AAA Single Piece Air Handler Ceiling Mount N Uncased Flowrater. Revision release all models of 13

Page 102

190WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 103

191WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 104

192WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 105

193WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 106

194WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 107

195WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 108

196WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 109

197WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 110

198WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 111 - *

199WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 112

Pride and workmanship go into every product to provide our customers with quality products. It is possible, however, thatduring its lifetime a produc

Page 113

PRODUCT IDENTIFICATION20Model # DescriptionARUF172916AAA24-00-2RCAA Single Piece R Multi-Position PSC Motor Unpainted Flowrater Introduction of new

Page 114

200WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 115

201WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 116

202WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 117

203WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 118

204WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 119

205WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 120

206WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 121

207WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 122

208WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 123

209WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 124

PRODUCT IDENTIFICATION21Model # DescriptionASPF****16AAA Single Piece S Multi-Position EEM motor Painted Flowrator. Introduces new ASPF Air HandlersA

Page 125

210WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 126

211WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 127

212WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 128

213WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 129

214WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 130

215WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 131

216WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 132

217WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 133

218WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 134

219WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 135

PRODUCT IDENTIFICATION22Model # DescriptionAVPTC183014AAAVPTC313714AAAVPTC426014AAA Single Piece V Multi-Position Variable-Speed Painted T TXV Flowra

Page 136

220WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 137

221WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 138

222WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 139

223WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 140

224WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 141

225WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 142

226WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 143

227WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 144 - ELECTRIC HEATER CAPACITY BTUH

228WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 145

229WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 146

PRODUCT IDENTIFICATION23Model # DescriptionAW UF****16AAA Single Piece Air Handler Wall Mount Unpainted Flowrator. Introduces 13 SEER Dayton wall mo

Page 147

230WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 148

231WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 149

232WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 150

233WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 151

234WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 152

235WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 153

236WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 154

237WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 155

238WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 156

239WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 157

PRODUCT IDENTIFICATION24Model # DescriptionMBR****AA-1AA Modular Blower R Multi-Position PSC Motor. Introduces module blower with PSC blower motor.

Page 158

240WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 159

241WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 160

242WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 161

243WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 162

244WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 163 - Strapping placed

245WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 164

246WIRING DIAGRAMSWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.DSX180[36-60]1A*USE N.E.C

Page 165 - Vertical

247WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 166

248WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 167 - PRESSURE DROP ACROSS COILS

249WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 168

PRODUCT IDENTIFICATION25Model # DescriptionCAUF*****6AAC Indoor Coil A Upflow/Downflow Uncased Flowrator. Introduces CAUF Dayton Upflow/Downflow coil

Page 169 - ACCESSORIES WIRING DIAGRAMS

250WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 170

251WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 171

252WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 172

253WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 173

254WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 174

255WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 175

256WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 176

257WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 177

258WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 178

259WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 179 - 25kW Heat Kit

PRODUCT IDENTIFICATION26Model # DescriptionCSCF*****6AAC Indoor Coil S Horizontal Slab Coil C Upainted Flowrator. Release 13 SEER CSCF slab horizont

Page 180 - AIRHANDLERS

260WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 181 - HIGH VOLTAGE!

261WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 182

262WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 183

263WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 184

264WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 185

265WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 186

266WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 187

267WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 188

268WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 189

269WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 190

PRODUCT IDENTIFICATION27SSZ14361AAPRODUCTTYPE:X: Condenser R-410AZ: Heat Pump R-410APRODUCTFAMILY:S: Split SystemSEER:SEER RatingBRAND:G: Goodman®(St

Page 191

270WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 192

271WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 193

272WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 194

273WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 195

274WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 196

275WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 197

276WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 198

277WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 199

278WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 200

279WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 201

PRODUCT IDENTIFICATION28ComfortNet™A S X C 16 024 1 A A PRODUCT TYPE: C: Condenser R-22 H: Heat Pump R-22 X: Condenser R-410A Z: Heat Pump R-410A

Page 202

280WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 203

281WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 204

282WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 205

283WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 206

284WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 207 - REMOTE - SPLITS

285WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 208

286WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 209

287WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 210

288WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 211

289WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 212

PRODUCT IDENTIFICATION29C A P T 3131 B 4 APRODUCTTYPE: C: Indoor Coil CABINET FINISH: P: Painted EXPANSION DEVICE: T: Factory installed n

Page 213

290WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 214

291WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 215

292WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 216

293WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 217

294WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 218

295WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 219

296WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 220

297WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 221

298WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 222

299WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 223

SAFE REFRIGERANT HANDLINGWhile these items will not cover every conceivable situation, they should serve as a useful guide.IMPORTANT INFORMATIONThe su

Page 224

PRODUCT IDENTIFICATION30MB R 8 00 A A 1DESIGN SERIES: MB: Modular Blower MOTOR TYPE: R: Constant Speed E: Variable Speed AIRFLOW DELIVERED 08

Page 225

300WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 226

301WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 227

302WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 228

303WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 229

304WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 230

305WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 231

306WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 232

307WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 233

308WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 234

309WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 235

PRODUCT IDENTIFICATION31All Airhandlers use DIRECT DRIVE MOTORS. Power supply is AC 208-240v, 60 hz, 1 phase.A W U F 3642 1 6 A APRODUCTTYPE:A: Air Ha

Page 236

310WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 237

311WIRING DIAGRAMSHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THISUNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TODO SO

Page 238

PRODUCT IDENTIFICATION32ARUF**14** / ARPT**14**/ASPT**14**Airhandlers use DIRECT DRIVE MOTORS. Power supply is AC 208-230v, 60 hz, 1 phase.ARUF18B14AA

Page 239

PRODUCT IDENTIFICATION33All Airhandlers use DIRECT DRIVE MOTORS. Power supply is AC 208-230v, 60 hz, 1 phase.ComfortNet™AV P T C 18B 14AA123456,789101

Page 240

PRODUCT IDENTIFICATION34LIGHT COMMERCIALModel # DescriptionGSX11090*AAGSX11120*AAGoodman Split X Condenser 11 Seer condensing units. Introduction of

Page 241

PRODUCT IDENTIFICATION35AR Nominal Cooling CapacityModel SeriesAR0904 - 90,000 Btuh (7 1/2 Tons)1204 - 120,000 Btuh (10 Tons)LIGHT COMMERCIALGSX110903

Page 242

ACCESSORIES36LIGHT COMMERCIALGSX11GSZ11NOTES:• AR Series Air Handlers do not have factory installed electric heat. Purchased as an accessory, these ar

Page 243

37ACCESSORIES1Contains 20 brackets; fourbrackets needed to anchor unitto pad2Installed on indoor coil.3Field-installed, non-bleed, ex-pansion valve ki

Page 244

ACCESSORIES38ASX14Model DescriptionASX14018ASX14024ASX14030ASX14036ASX14042ASX14048ASX14060ABK-201Anchor Bracket Kit XXXXXXXASC01Anti-Short Cycle Kit

Page 245

39ACCESSORIESSSX16Model DescriptionSSX16024*SSX16030*SSX16036*SSX16042*SSX16048*SSX16060*ABK-201Anchor Bracket Kit XXXXXXASC01 Anti-Short Cycle KitXXX

Page 246

PRODUCT IDENTIFICATION4Model # DescriptionASZ130**1AAAmana® Brand Split Z R410A heat pump 13 Seer heat pump units. Initial release of Amana® Brand 13

Page 247

ACCESSORIES40ASX/DSX18Model DescriptionA/DSX18036*A/DSX18048*/DSX18060*ABK-201Anchor Bracket Kit X X XASC01 Anti-Short Cycle KitXXXCSR-U-1 Hard-start

Page 248

41ACCESSORIESComfortNet™Model DescriptionASXC16024DSXC16024ASXC16036DSXC16036ASXC16048DSXC16048ASXC16060DSXC16060ASXC18036DSXC18036ASXC18048DSXC18048A

Page 249

ACCESSORIES421Contains 20 brackets; four bracketsneeded to anchor unit to pad2Installed on indoor coil.3Required for heat pump applicationswhere ambie

Page 250

43ACCESSORIESSSZ14Model DescriptionSSZ14018*SSZ14024*SSZ14030*SSZ14036*SSZ14038*SSZ14042*SSZ14048*SSZ14060*AFE18-60AAll-Fuel Kit XXXXXXX XCSR-U-1 Hard

Page 251

ACCESSORIES44ASZ16/DSZ16Model DescriptionA/DSZ16024*A/DSZ16030*A/DSZ16036*A/DSZ16042*A/DSZ16048*A/DSZ16060*AFE18-60A All-Fuel Kit X X X X X XCSR-U-1 H

Page 252

45ACCESSORIESASZ/DSZ18Model DescriptionA/DSZ18036*A/DSZ18048*A/DSZ18060*AFE18-60A All-Fuel Kit X X XCSR-U-1 Hard-start Kit XCSR-U-2 Hard-start Kit XCS

Page 253

ACCESSORIES46ComfortNet™Model DescriptionASZC16024DSZC16024ASZC16036DSZC16036ASZC16048DSZC16048ASZC16060DSZC16060ASZC18036DSZC18036ASZC18048DSZC18048A

Page 254

47ACCESSORIES SUCTION LINE BULB 1/4 FLARE CONNECTION EXPANSION VALVE EVAPORATOR COIL REMOVE BEFORE INSTALLING EXPANSION VALVESEAL SUPPLIED W/ KITSEA

Page 255

ACCESSORIES48FSK01AFREEZE THERMOSTATKITT2 T1L2L1BLACK 1THERMOSTATWIRESHORT CYCLEPROTECTORYELLOW 1BLACK 1Y1Y2R1R2YCUNITTERMINALBOARDCONTACTORASC01AANTI

Page 256

49ACCESSORIESCOIL ACCESSORIESCOIL MODELTX2N4ATXV KITTX 3N4TXV KITTX5N4TXV KITFSK01A FREEZE PROTECTION KITCA*F18246* XXCA*F30306* XXCA*F31316*CA*F3636

Page 257

PRODUCT IDENTIFICATION5Model # DescriptionASZ160**1AAAmana® Brand Split Z R410A heat pump 16 Seer heat pump units. Initial release of Amana® Brand 16

Page 258

ACCESSORIES50ELECTRIC HEAT KIT APPLICATIONS - ARUFELECTRIC HEAT KIT APPLICATIONS - ARPFARUF1729 1/16ARUF1824 1/16ARUF1931 1/16ARUF3030 1/16ARUF3642

Page 259

51ACCESSORIESELECTRIC HEAT KIT APPLICATIONS - AVPTC* Revision level that may or may not be designated.C Circuit breaker option.ELECTRIC HEAT KIT APP

Page 260

ACCESSORIES52ELECTRIC HEAT KIT APPLICATIONS - ASPFDRAIN PAN INSULATION KITS - ARUF**14**, ARPT**14**, ASPT**14** & ASUF**14**DFK-BDownflow KitD

Page 261

53ACCESSORIESARPT**14**Heat Kit ApplicationsType / model 18B14-A* 24B14-A* 30B14-A* 36C14-A* 36D14-A* 42D14-A* 48D14-A* 60D14-A*HKSX03XC* XXXXXXXXHKSX

Page 262

ACCESSORIES54ARUF**14**3 5 6 8 101519202518 715 715 715 715 95024 715 715 715 715 95030B 715 715 715 715 875 87530C 1170 1170 1170 1170 1345 134536 11

Page 263

55ACCESSORIESASUF**14**3 5 6 8 10 15 19 20 2529 71 5 715 715 7 15 87539 1170 11 70 1170 1 17 0 134 5 134549 1170 11 70 1170 1 17 0 134 5 134559 1590 1

Page 264

ACCESSORIES56ASPT**14**3 5 6 8 10 15 19 20 25ASPT24B14715 715 715 715 875 NR NR NR NRASPT30C14730 715 715 715 950 NR NR NR NRASPT36C14NR 1170 1170 117

Page 265

57ACCESSORIES3 5 6 8 10 15 19 20 21 or 25AVPTC24B14 550 650 700 800 850 NR NR NR NRAVPTC30C14 600 700 750 875 950 NR NR NR NRAVPTC36C14 NR 850 900 100

Page 266

PRODUCT DESIGN58This section gives a basic description of cooling unit opera-tion, its various components and their basic operation.Ensure your system

Page 267

PRODUCT DESIGN59The ASX & ASXC [16 & 18], ASZ & ASZC [16 & 18], DSX &DSXC [16 & 18] and DSZ & DSZC [16 & 18] series sp

Page 268

PRODUCT IDENTIFICATION6Model # DescriptionASZC160**1AAAmana® brand Split Z Communicating heat pump, 16 Seer R410A heat pum p units. Introduces Goodma

Page 269

PRODUCT DESIGN60CAPACITY CONTROL - LEGACY MODELSDuring the compression process, there are several pocketswithin the scroll that are compressing gas. M

Page 270

SYSTEM OPERATION61COOLINGThe refrigerant used in the system is R-410A. It is a clear,colorless, non-toxic and non-irritating liquid. R-410A is a50:50

Page 271

SYSTEM OPERATION62When the thermostat is satisfied, appropriate commands aresent to the UC control. The compressor relay and outdoorfan relay is de-

Page 272

SYSTEM OPERATION63COOLING CYCLEHEATING CYCLEIndoorCoilAccumulatorBi-FlowFilter DryerOutdoorCoilThermostaticExpansionValveCheck ValveReversing Valve(De

Page 273

SYSTEM OPERATION64RESTRICTOR ORIFICE ASSEMBLYIN COOLING OPERATIONRESTRICTOR ORIFICE ASSEMBLYIN HEATING OPERATIONIn the cooling mode, the orifice is pu

Page 274

SYSTEM OPERATION65AFE18-60A CONTROL BOARDDESCRIPTIONThe AFE18 control is designed for use in heat pump applica-tions where the indoor coil is located

Page 275

66TROUBLESHOOTING CHARTCom plaintSystem Operating PressuresPOSSIBLE CAUSEDOTS IN ANALYSISGUIDE INDICATE"POSSIBLE CAUSE"SYMPTOMSystem will no

Page 276 - CONTROL BOX

SERVICING67HIGH VOLTAGE!Disconnect ALL power before servicing or installing. Multiple power sources may be present. Failure todo so may cause property

Page 277

SERVICING68S-1 CHECKING VOLTAGE1. Remove outer case, control panel cover, etc., from unitbeing tested.With power ON:WARNINGLine Voltage now present.2.

Page 278

SERVICING69Indoor Blower MotorWith power ON:WARNINGLine Voltage now present.1. Set fan selector switch at thermostat to "ON" position.2. Wit

Page 279

PRODUCT IDENTIFICATION7Model # Descrip tionDSZ160**1AADeluxe Spl it Z Heat Pum p 16 Seer heat pump units. Introduces Goodman 2-stage 16 SEER heat pu

Page 280

SERVICING7012RC12RC12RCCTK0*ThermostatCT™ CompatibleModular BlowerIntegrated Control ModuleCT™ Compatible AC/HPIntegrated Control ModuleSystem Wiring

Page 281

SERVICING71To exit an equipment submenu and revert back to theequipment menus, touch the Menu key. Touch Menu againto revert back to the Thermostat O

Page 282

SERVICING72Submenu Item Indication (for Display Only; not User Modifiable)Electric Heat Size (HTR KW) Displays the size in kW of the selected electric

Page 283

SERVICING73Submenu Item User Modifiable Options CommentsOutdoor Air Temperature(AIR TMP)Displays the outdoor air temperatureSensor may or may not be a

Page 284

SERVICING74Submenu Item Indication (for Display Only; not User Modifiable)Mode (MODE) Displays the current air conditioner operating modeCFM (CFM) Dis

Page 285

SERVICING75S-5 CHECKING CYCLE PROTECTORSome models feature a solid state, delay-on make after breaktime delay relay installed in the low voltage circu

Page 286

SERVICING763. Using a voltmeter, test across terminals.A. L2 - T1 - No voltage indicates CC1 contacts open.If a no voltage reading is obtained - repl

Page 287

SERVICING77Condenser fan control for the ASXC/ASZC and DSXC/DSZCmodels is fully integrated into the UC control. The controlsupports one- or two-speed

Page 288

SERVICING78 Schematic Abbreviation DescriptionsHTCO High Temperature Cut Out SwitchHPCO High Pressure Cut Out SwitchLPCO Low Pressure Cut Out S

Page 289

SERVICING79Status LED Status LED Description Status LED Troubleshooting InformationGreen “POWER” Module has power Supply voltage is present at modul

Page 290

PRODUCT IDENTIFICATION8Model # DescriptionGSZ13**1AA Goodman Split Z R410A Heat Pump 13 Seer heat pump units. Initial release with Regal Beloit moto

Page 291

SERVICING80DIAGNOSTICS - 2-WIRE MODULEApplies to ASX130[18-60]CA, ASX140[18-36]1CA,ASX140421DA, and ASX140[48-60]1BA unitsComfort Alert™ is self-cont

Page 292

SERVICING81Status LED Status LED Description Status LED Troubleshooting InformationGreen “POWER” Module has power Supply voltage is present at module

Page 293

SERVICING82S-10A COPELAND COMFORT ALERTTM -UNITARY (UC) CONTROL DIAGNOSTICSApplies to ASXC, ASZC, DSXC, and DSZC modelsHIGH VOLTAGE!Disconnect ALL pow

Page 294

SERVICING83Symptoms of Abnormal Operation (Legacy & ComfortNet™ Thermostat) Diagnostic/Status LED Codes Faul t Description Co mf o rt Net™ Thermos

Page 295

SERVICING84Diagnostic/Status LED Codes ComfortNet™ Thermostat Only Symptoms of Abnormal Operation (Legacy & ComfortNet™ Thermostat) Green Yellow

Page 296

SERVICING85Diagnostic/Status LED Codes ComfortNet™ Thermostat Only Symptoms of Abnormal Operation (Legacy & ComfortNet™ Thermostat) Green Yellow

Page 297

SERVICING86Diagnostic/Status LED Codes Com f or tNe t ™ Thermostat Only Symptoms of Abnormal Operation (Legacy & ComfortNet™ Thermostat) Green Ye

Page 298

SERVICING87Diagnostic/Status LED Codes Com f o r tNet™ Thermostat Only Symptoms of Abnormal Operation (Legacy & ComfortNet™ Thermostat) Green Yel

Page 299

SERVICING885.)4!29$)!'./34)##/$%33YMPTOMSOF!BNORMAL/PERATION,EGACY#OMFORT.ET4HERMOSTAT$IAGNOSTIC3TATUS,%$$ISPLAY#ODES&AULT

Page 300

SERVICING895.)4!29$)!'./34)##/$%33YMPTOMSOF!BNORMAL/PERATION,EGACY#OMFORT.ET4HERMOSTAT$IAGNOSTIC3TATUS,%$$ISPLAY#ODES &AULT

Page 301

PRODUCT IDENTIFICATION9Model # DescriptionSSZ140**1AASpecial High Feature Split Z R410A heat pump 14 Seer heat pump units. Initial release of Goodman

Page 302

SERVICING905.)4!29$)!'./34)##/$%33YMPTOMSOF!BNORMAL/PERATION,EGACY#OMFORT.ET4HERMOSTAT$IAGNOSTIC3TATUS,%$$ISPLAY#ODES &AULT

Page 303

SERVICING91Compressor and outdoor f. Low pressure switch trip 3 times within same thermostat demand. Thermostat demand is present. Integrated contr

Page 304

SERVICING92 Run time for last 4 cycles is less than 3 minutes each.Compressor protector has not tripped.Low pressure and high pressure switches are cl

Page 305

SERVICING93Compressor and outdoor f .Low pressure and high pressure switches are closed.Open start circuit has been detected 4 times with 5 minute del

Page 306

SERVICING94Air conditioner/heat pump may appear to be operating normally. Compressor protector may be open (compressor and outdoor f Integrated cont

Page 307

SERVICING950140M00407-A7 SEGMENT LED (DS2)7 SEGMENT LED (DS1)DESCRIPTION OF CONDITION0 n Standby0 1 Low Pressure CO Trip0 1 Low Side Fault0 2 High

Page 308

SERVICING96S-10B COPELAND CORESENSE™DIAGNOSTICS - 3-WIRE MODULEApplies to ASX /ASZ and DSX/DSZ unitsThe CoreSense™ module is self-contained with no r

Page 309

SERVICING97DIAGNOSTICS TABLE: CORESENSE™ MODULEFlash code number corresponds to the number of LED flashes, followed by a pause and then repeated.TRIP

Page 310

SERVICING98DIAGNOSTICS TABLE: CORESENSE™ MODULE (cont.)Flash code number corresponds to the number of LED flashes, followed by a pause and then repea

Page 311

SERVICING99 Table 1 - Quick Reference Table