Servicer’s Note
CAUTION
Avoid servicing the low ambient control
while the unit is operating. The rotating
fan blades could cause serious injury.
If measurement of the high side pressure is required, use
the liquid line valve on the outside of the unit. Also note
that most electrical measurements for the compressor
can be performed adequately near the contactor, rather
than at the compressor itself. If you must service the
area near the compressor or low ambient control with the
unit in operation, consider doing the following:
Disconnect the electrical power
Unplug the outdoor fan motor.
Carefully reconnect the electrical power.
Operate the compressor only long enough to com-
plete the needed service function.
NOTE: Running the system without outdoor airflow will
cause the head pressure to be substantially higher than
normal. Suction pressure and amp draw will also be
higher than normal. Subcooling, however, will be less
than normal.
outdoor fan will continue to run as long as the
compressor runs. During cool weather, the head
pressure will drop after the outdoor fan comes on. If
the head pressure drops to about 100 psi, the outdoor
fan will shut off. The head pressure will then begin
to rise. The outdoor fan will restart when the head
pressure rises to about 220 psi.
If any sparking, unusual odors, or unusual sounds are
noticed, immediately disconnect the electrical power
and check wiring and electrical components.
With the compressor running, it may be advisable to
perform a final leak check on the low ambient cutout and
nearby components. Before doing this, read the
“Servicer’s Note” section that follows.