ProduCT sPeCifiCATions: PTH models — reverse-CyCle HeATing PerformAnCe
Notes:
¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
² Minimum Circuit Ampacity (MCA) rangs conform to the Naonal Electric Code; however, local codes should apply.
³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.
Minimum voltage on 265-volt models is 238.5 volts; maximum is 291.5 volts.
⁴ Overcurrent protecon for all units without electric heaters is 15 amps. Overcurrent protecon on 265-volt models must be cartridge-style me-delay
fuses (included and factory-installed on all Amana® brand 265-volt chassis). See heater performance for total MCA.
⁵ Heang capacity and eciency based on unit operaon without condensate pump; unit automacally switches to electric heat
at approximately 24°F outdoor ambient.
⁶ Total was for 12,000 and 15,000 BTU/h models; subtract 70 was for PT07/09*E**A*
⁷ Specify two-digit heater kW size to complete model number.
⁸ Total amps for 12,000 and 15,000 BTU/h models; subtract 0.2 amps for PT07/09*E*A*.
⁹ R-410A refrigerant used in all systems.
¹⁰ All units meet or exceed ASHRAE 90.1 standards.
¹¹ All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
¹² Refer to electric heat performance data for total MCA and recommended overcurrent protecon. Amps and Was notaon refers to compressor only.
230/208 Volts
Heating Capacity
PTH
073E**AXXX
PTH
093E**AXXX
PTH
123E**AXXX
PTH
153E**AXXX
Voltage ³ 230 / 208 230 / 208 230 / 208 230 / 208
BTU/h
⁵ 6,800 / 6,800 8,300 / 8,100 10,900 / 10,500 13,500 / 13,300
Amps
¹⁰ 3.5 / 3.5 4.1 / 4.1 5.6 / 5.6 7.0 / 7.0
Was
¹⁰ 605 / 605 735 / 720 1040 /1020 1365 / 1345
COP
5
3.3 / 3.3 3.3 / 3.3 3.1 / 3.1 2.9 / 2.9
CFM (Dry) 310 310 310 360
265/277 Volts
Heating Capacity
PTH
074E**AXXX
PTH
094E**AXXX
PTH
124E**AXXX
PTH
154E**AXXX
Voltage ³ 265 265 265 265
BTU/h
⁵ 6,800 8,200 11,000 13,500
Amps
¹⁰ 3.0 3.6 4.8 6.0
Was
¹⁰ 585 730 1040 1365
COP
⁵ 3.4 3.3 3.1 2.9
CFM (Dry) 310 310 310 360
COP = Coeciency of Performance; per ARI test procedures, units are rated for capacies and eciencies.