Product Specifications: PTH Models — Reverse-Cycle Heating Performance
H
C
PTH073G
**AXXX
PTH093G
**AXXX
PTH123G
**AXXX
PTH153G
**AXXX
PTH074G
**AXXX
PTH094G
**AXXX
PTH124G
**AXXX
PTH154G
**AXXX
Voltage
,
230 / 208 230 / 208 230 / 208 230 / 208 265 265 265 265
BTU/h 6,800 / 6800 8,300 / 8,100 11,500 / 11,300 13,800 / 13,600 6,800 8,300 11,400 13,700
Amps 3.9 / 3.9 4.2 / 4.2 5.8 / 5.8 7.0 / 7.0 3.1 3.7 5.0 6.1
Watts 585 / 585 715 / 700 1085 /1035 1350 / 1330 585 715 1080 1340
COP 3.4 / 3.4 3.4 /3.4 3.1 / 3.2 3.0 / 3.0 3.4 3.4 3.1 3.0
CFM (Dry) 370 360 370 410 370 360 370 410
COP = Coeiciency of Performance; per AHRI Test Procedures, units are rated for capacities and eiciencies.
N
All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
Minimum branch circuit ampacity ratings conform to the National Electric Code; however, local codes should apply.
Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.
Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must
be cartridge-style time-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis).
Heating capacity and eiciency based on unit operation without condensate pump; unit automatically switches to electric
heat at approximately 24°F outdoor ambient.
Specify two-digit heater kW size to complete model number.
R-410A refrigerant used in all systems.
All units meet or exceed ASHRAE 90.1 standards.
All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
Refer to electric heat performance data for total MCA and recommended overcurrent protection.
Amps and Watts notation refers to compressor only.
Product Specifications: PTC / PTH Models — Electric Heat Performance
(Primary Heating for PTC Models; Auxiliary Heating for PTH Models; See below for Power Cord Configuration)
V
E
H
S (W)
N.
S
N H (BTU/)
T
W
T
A
M. C
A
MOP
()
P
C
@ V @ V @ V
230/208V 1.5 / 1.3 1 5,100 4,200 - - 1,570 / 1,295 6.8 / 6.2 8.5 15 6-15 P
230/208V 2.5 / 2.1 1 8,500 6,800 - - 2,570 / 2,115 11.2 / 10.1 14.1 15 6-15 P
230/208V 3.5 / 3.0 1 12,000 9,900 - - 3,570 / 2,935 15.5 / 14.1 19.5 20 6-20 P
230/208V 5.0 / 4.1 1 17,100 14,000 - - 5,070 / 4,160 22.1 / 20.0 27.6 30 6-30 P
265V 1.5 1 - - - - 5,100 1,570 5.9 7.4 15 7-20P
265V 2.5 1 - - - - 8,500 2,570 9.7 12.2 15 7-20 P
265V 3.7 1 - - - - 12,600 3,770 14.2 17.9 20 7-20 P
265V 5 1 - - - - 17,100 5,070 19.2 23.9 25 7-30 P
N
All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
Minimum branch circuit ampacity ratings conform to the National Electric Code; however, local codes should apply.
Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style
time-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis).
Heating capacity and eiciency based on unit operation without condensate pump; unit automatically switches to electric heat at
approximately 24°F outdoor ambient.
Total watts for 15,000 BTU/h models; subtract 20 watts for PT07/09/12
Specify two-digit heater kW size to complete model number.
R-410A refrigerant used in all systems.
All units meet or exceed ASHRAE 90.1 standards.
All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.