RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
ATTENTION INSTALLING PERSONNEL
Prior to installation, thoroughly familiarize yourself with this Installation Manual. Observe all safety warnings. During
installation or repair, caution is to be observed.
It is your responsibility to install the product safely and to educate the customer on its safe use.
These installation instructions cover the outdoor
installation of self contained package air conditioners
and heating units. See the Specification Sheets
applicable to your model for information regarding
accessories.
Goodman Manufacturing Company, L.P.
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com www.amana-hac.com
© 2010 Goodman Manufacturing Company, L.P.
I
NSTALLATION
I
NSTRUCTIONS
F
OR
S
ELF
-C
ONTAINED
P
ACKAGE
A
IR
C
ONDITIONERS
AND
H
EAT
P
UMP
U
NITS
GPC/GPH 13 SEER “M” SERIES
W
ITH
R-410A
IO-395A
12/10
Page view 0
1 2 ... 16

Summary of Contents

Page 1

CUS®*NOTE: Please contact your distributor or ourwebsite for the applicable Specification Sheetsreferred to in this manual.RECOGNIZE THIS SYMBOL AS

Page 2 - WARRANTY

10supplementary heat for all heat pump installations in areas wherethe temperature drops below 45° F. It is also a good practice toprovide sufficient

Page 3 - CODES AND REGULATIONS

11NOTES:• Data shown is dry coil.Wet coil pressure drop isapproximately:0.1” H20, for two-row indoorcoil;0.2” H2O, for three-rowindoor coil;and 0.3” H

Page 4

12SPEED TAP ADJUSTMENTS FOR INDOOR BLOWER MOTORPSC MotorAdjust the CFM by changing the speed tap of the indoor blowermotor at the EBTDR “COM” connecti

Page 5 - AIRFLOW C ONVERSION

13Unit Model Number 5 8 10 15 20GPH1324M41**M(F)M(F)M(F)HNAGPH1330M41**M(F)M(F)M(F)HNAGPH/GPC1336M41**MMH(F )H(F )NAGPH1342M41**MMH(F )H(F )NAGPH/GPC1

Page 6 - CONDENSATE D RAIN

14TROUBLESHOOTING CHARTSYMPTOMHigh head - low suction a. Restriction in liquid line or flowrator a. Remove or replace with proper size flowrator.High

Page 7 - INTERNAL W IRING

15APPENDIXUNIT DIMENSIONSMEDIUM CHASSISGP*1324M4**GP*1330M4**GP*1336M4**GP*1342M4**LARGE CHASSISGP*1348M4**GP*1360M4**BLOWERACCESS PANEL??2 345147SUPP

Page 8 - COMPONENTS

16MINIMUM CLEARANCESRECOMMENDED FILTER SIZES3"MIN12" MIN36" MIN(FOR SERVICE).48" MIN12" MIN 36" MIN(FORSERVICE) NOTE: R

Page 9 - HEATING CYCLE

2WARNINGINSTALLATION AND REPAIR OF THIS UNIT SHOULD BEPERFORMED ONLY BY INDIVIDUALS MEETING THE REQUIREMENTS OF AN “ENTRY LEVEL TECHNICIAN” ASSPECIFIE

Page 10 - DEFROST C ONTROL

3“Product Registration” located on the left side of the Warrantypage and complete the forms in the manner indicated on theProduct Registration page.Pr

Page 11

4The information on the rating plate is in compliance with the FTC& DOE rating for single phase units. The three phase units inthis series are not

Page 12 - ELECTRICAL ADJUSTMENTS

5Rooftop InstallationROOF CURB INSTALLATIONS O NLYNOTE: Sufficient structural support must be determined prior tolocating and mounting the curb and pa

Page 13 - HIGH VOLTAGE!

6Remove these coversfor horizontal ductapplicationsRemove these panelsfor downflow ductapplicationsSupplyReturnDuct Cover InstallationDown Discharge A

Page 14 - TROUBLESHOOTING CHART

7WIRINGNOTE: All wiring should be made in accordance with the NationalElectrical Code.Consult your local Power Company to determine the availability o

Page 15 - UNIT DIMENSIONS

8BRANCH CIRCUIT AMPACITY15 20 25 30 35 40 45 50SUPPLY WIRE LENGTH - FEET200 64443322150 86644433100 10886664450 1412101088662. Wire size based on 60°

Page 16 - RECOMMENDED FILTER SIZES

9crankcase thereby preventing liquid migration and subsequentcompressor damage. The insert type heater is self regulating. It isconnected electricall