Comfort. Quality. Trust.
Heating
®
&Air Conditioning
Amana
1810 Wilson Parkway • Fayetteville, TN 37334
May 2001 10664122
DESCRIPTION
This kit is for use with Amana VCA and RCB remote cooling
units that do not have high or low pressure cutouts or
factory-installed anti short-cycle protector. The Anti Short-
Cycle Control kit (ASC) prevents short cycling of the com-
pressor. The Pressure Control Kit (PCK) helps protect the
compressor from damage due to abnormally high or low
refrigerant pressures. It also prevents short cycling of the
compressor.
Although it is not mandatory, we recommend that this kit be
installed before the refrigerant lines are connected to the
outdoor unit, and before the line and low voltage wiring is
connected to the outdoor unit.
PCK kits include a high pressure cutout, a low pressure
cutout, and an anti short-cycle control. It also includes tees
for mounting the pressure cutouts on the outdoor unit
service valves. After the tees are installed, a gauge mani-
fold can be attached to them when servicing is necessary.
The ASC kit contains a anti short-cycle protector for use on
units with reciprocating compressors.
NOTE: Units with scroll compressors have ASC protectors
installed at the factory.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
ATTENTION INSTALLING PERSONNEL
As a professional installer you have an obligation to
know the product better than the customer. This
includes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize
yourself with this Instruction Manual. Pay special
attention to all safety warnings. Often during
installation or repair it is possible to place yourself
in a position which is more hazardous than when
the unit is in operation.
Remember, it is your responsibility to install the
product safely and to know it well enough to be able
to instruct a customer in its safe use.
Safety is a matter of common sense...a matter of
thinking before acting. Most dealers have a list of
specific good safety practices...follow them.
The precautions listed in this Installation Manual
are intended as supplemental to existing practices.
However, if there is a direct conflict between existing
practices and the content of this manual, the
precautions listed here take precedence.
BILL OF MATERIAL
PCK01A ASC01A
2 Refrigerant Tees, w/valvcores
1 Low Pressure Cutout, Auto Reset
1 High Pressure Cutout, Auto Reset
1 Short Cycle Protector
1 Yellow-1 Wire
1 Black-1 Wire
1Wire Nut
1 Wiring Diagram Label
1 Installation Instructions
1 Sheet Metal Screw
4 Teflon Seals
1 Extension Tube
These kits should only be installed by a qualified, experi-
enced technician.
ASC01A
Anti Short-Cycle Control
PCK01A
Pressure Control Kits
Installation Instructions