Amana AMV8 Technical Information Page 15

  • Download
  • Add to my manuals
  • Print
  • Page
    / 17
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 14
BLOWER PERFORMANCE SPECIFICATIONS
15
30 40 50 60 70 80 90 110 120
100
130 140 150
100
90
80
70
60
50
40
30
20
10
OUTPUT BTU/HR x 1000
BTU OUTPUT vs TEMPERATURE RISE CHART
TEMPERATURE RISE
600 CFM
700
900
1000
1100
1200
1400
1600
1800
2000
2200
2400 CFM
FORMULAS
BTU OUTPUT = CFM x 1.08 x RISE
RISE =
BTU OUTPUT
1.08
÷ CFM
800
Page view 14