Amana VTC Series Owner's Manual Page 3

  • Download
  • Add to my manuals
  • Print
  • Page
    / 9
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 2
3
Unit Features
This unit has many features which are different than those
found on conventional units. The servicer must be familiar
with these features in order to properly service the unit.
Random restart delay - The SPVU employs a random
reset timer which delays unit operation up to 3 minutes
following initial power application. Electronic thermo-
stats may also employ internal reset timers which may
further delay any changes which are made to the
operation of the unit.
Automatic 3-minute compressor lockout - After the
compressor cycles off, it will not restart for three min-
utes. Additional delays may be experienced if using an
electronic digital thermostat.
Low ambient compressor lockout - When the outdoor
ambient temperature is below 40 degrees F, the low
ambient compressor lockout switch will keep the com-
pressor from energizing in either cooling or heat pump
mode.
Direct drive, multi-speed blower - The proper speeds
have been preset at the factory for heating and cooling.
Refer to wiring diagram for recommended blower
speeds for specific models.
Condensate Drain - This unit comes with a factory
installed drain tubing installed on the bottom of the unit.
This tubing drains from a trap at the bottom of the
condenser section.
Unit Location
Provisions should be made to allow access to the indoor
side of the unit for installation and inspection. The closet or
access panel opening must be centered with the exterior
wall opening and at least 24” wide by 84” tall. Three (3)
inches of unobstructed space is required on all sides of the
SPVU to allow for adequate air flow. At least 27 inches of
unobstructed space should be provided in front of the access
door to permit removal of the unit should repair and
inspection be required.
Transportation Damage
The SPVU is shipped in one package, completely as-
sembled. Material in this shipment has been inspected at
the factory and released to the transportation agency in
good condition. When received, a visual inspection of all
cartons should be made immediately. Any evidence of
rough handling or apparent damage should be noted on the
delivery receipt and the material inspected in the presence
of the carrier’s representative. If damage is found a claim
should be filed against the carrier immediately.
In the event of damage, the consignee should:
1. Make notation on delivery receipt of any visible dam-
age to shipment or container.
2. Notify carrier promptly and request an inspection.
3. In case of concealed damage, carrier must be notified
as soon as possible—preferably within 5 days.
4. File the claim with the following supporting documents
within the 6 month statute of limitations.
a. Original Bill of Lading, certified copy, or indemnity
bond.
b. Original paid freight bill or indemnity in lieu thereof.
c. Original invoice or certified copy thereof, showing
trade and other discounts or reductions.
d. Copy of the inspection report issued by carrier’s
representative at the time damage is reported to the
carrier
The carrier is responsible for making prompt inspection of
damage and for a thorough investigation of each claim.
The distributor or manufacturer will not accept claims from
dealers for transportation damage.
Unit Accessories
This unit is designed for through-the-wall installation in new
or existing buildings. To complete the installation of this
unit, a wall sleeve, an architectural grille, thermostat and a
filter are required.
The unit is shipped in one carton. Optional accessories to
complete a particular installation are the following:
Optional Accessories
Louvered Grille Freeze Sensor
Non-Louvered Grille Access Return Air Grille
60° Room Temperature Limiter
NOTE: Consult sales literature for the appropriate voltage
and amperage selections, if applicable.
Page view 2
1 2 3 4 5 6 7 8 9

Comments to this Manuals

No comments