ATTENTION INSTALLING PERSONNELAs a professional installer you have an obligation toknow the product better than the customer. Thisincludes all safety
2I. Safety InformationImportantTO THE INSTALLERBefore installing this unit please read this manual and theSpecification Sheet to familiarize yourself
3The unit should be carefully inspected upon arrival fordamage and bolts or screws which may have loosened intransit. In the event of damage, the con
4sun, television, etc. Consult the Instruction Sheet pack-aged with thermostat for mounting instructions.WARNINGTo avoid death or personal injury due
5Figure 3Low Voltage Terminal BoardWiring DiagramYL YELLOWOR ORANGEVT VIOLETGN GREENBK BLACKBR BROWNWH WHITEBU BLUEGY GRAYRD REDCOLOR CODELOW VOLTAGEL
6Units are shipped from the factory ready for horizontalairflow. If conversion to vertical airflow is necessary, pro-ceed as follows:1. Cut insulation
7NOTE: If Horizontal Duct Cover kits are required, align thehorizontal duct covers (Figure 9) over the flange bracketsjust installed and secure with
8Compressor Protection DeviceThe PCC**C compressor includes components which aredesigned to protect the compressor against abnormaloperating condition