AmanaFayetteville, TN 37334!RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.ATTENTION INSTALLING PERSONNELAs a professional installer you have an obligat
10• The temperature rise for each heating speed mustbe within the range specified on the rating plate orSpecification Sheet.NOTE: Air temperature rise
2I. DescriptionHANG07, HALP09, and HAC1PS01-14 conversion kits arerequired when installing the following units above theirmaximum rated altitudes:Aman
3Table 2Pressure Switch Kits (Category I Venting Only)HAC1PSNat. GasDerates(See Sec. V)01 02 03 04 05 06 07 08 09 10 11 12 13 14GUI(A/B)045(A/B)7501 -
4HATS01 HATS02 HATS03 HATS04 HATS05 HATS06 HATS07 HATS08 HATS09GUI(S,V)070 X XGUI(S,V)090 X XGUI(S,V)115 X XGUI(S,V)140 X XGCIS070 X XGCIS090 X XLow P
5FurnaceModel Kit NumberAltitude(Feet)OrificeGUIAGUIBGCIAGCIBHANG07 7501 - 11000 #45GUICGCICGUIDPGA/B/D**CHANG07 6001 - 11000 #45NOTE: Units Installed
6CAUTIONTo prevent unsatisfactory furnaceoperation, the proper gas conversion kitmust be used for each valve. Use the White-Rodgers spring kit only wi
7OFFONMPC132INLETPressure RegulatorAdjustment (Under Cap Screw)Inlet Pressure Tap (Side of Valve)Outlet (Manifold)Pressure Tap (Side of Valve)Gas Valv
8V. Operational Check1. Start the furnace using the procedures in the section,“Operating Your Furnace” in the installation instruc-tions. In addition,
9Derating Example 1: GUIA115A40 at 8500 ft.Sea level input = 115,000 BTU/Hr.From Table 2: Derate at 8500 ft. = 27±4%Since we are at the mid point of t