Amana PTC093E35AXXXAB Specifications Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 69
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
5
SPECIFICATIONS
NOTES:
1. All 265V models must use Amana’s subbase (PTSB4**C) or Amana’s hard wire kit (PTPWHWK4).
2. Minimum branch circuit ampacity rating conform to the National Electric Code. However, local codes should apply.
3. Minimum voltage on 230/208 volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5
volts.
4. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time
delay fuses (included and factory installed on Amana chassis).
5. Heating capacity and efficiency are based on unit operation without condensate pump. Unit automatically switches to electric heat at 25°F
outdoor coil temperature.
6. Total watts for 15,000 Btuh models; subtract 30 watts for PT12*A**AA and 70 watts for PT07/09*A**AA.
7. Please specify 2-digit heater kW size to complete model number.
8. Total amps for 12,000 and 15,000 Btuh models; subtract 0.2 amps for PT07/09*A*AA.
EER - Energy Efficiency Ratio per American
Refrigeration Institute (ARI) Test
Procedures and Canadian Standards
Association (CSA) Test Procedures
COP - Coefficient of Performance per ARI Test
Procedures
PTH073A**AA PTH074A**AA PTH093A**AA PTH094A**AA PTH123A**AA PTH124A**AA PTH153A**AA PTH154A**AA
Voltage
1&3
230/208 265 230/208 265 230/208 265 230/208 265
Capacity (BUTH)
7,400/7,200 7,400 9,000/8,800 9,000 12,000/11,600 12,000 14,000/13,800 14,000
Amps
2.5/2.6 2.0 3.5/3.8 3.0 4.6/5.0 3.7 7.4/7.9 6.5
Watts
625/610 625 810/790 810 1,145/1,125 1,145 1,490/1,470 1490
EER
11.5 11.5 11.1 11.1 10.6 10.6 9.4 9.4
UNIT WITHOUT
ELECTRIC HEATER
Minimum Circuit Ampacity
2&4
4.0 3.3 4.8 4.1 7.3 5.7 8.4 7.7
CFM
HIGH 220/215 220 220/215 220 290/270 290 325/315 325
LOW 175/155 175 175/155 175 220/190 220 250/220 250
HIGH 235/230 235 235/230 235 310/290 310 345/335 345
LOW 185/165 185 185/165 185 235/205 235 265/235 265
35 35 35 35 45 45 50 50
Dehumidification
(pints/hr)
1.9 1.9 2.7 2.7 3.8 3.8 4.4 4.4
Net Weight
110 110 120 120 130 130 140 140
Shipping Weight (approx.
lbs.)
130 130 140 140 150 150 160 160
Cool, Wet Coil
COOLING DATA (HEAT PUMP)
Ventilated Air
Dry Coil
PTC073A**AA PTC074A**AA PTC093A**AA PTC094A**AA PTC123A**AA PTC124A**AA PTC153A**AA PTC154A**AA
Voltage
1&3
230/208 265 230/208 265 230/208 265 230/208 265
Capacity (BUTH)
7,500/7,400 7,500 9,000/8,800 9,000 12,200/12,000 12,200 14,200/14,000 14,200
Amps
2.5/2.6 2.0 3.5/3.8 3.0 4.6/5.0 3.7 7.4/7.9 6.5
Watts
625/610 625 810/790 810 1,145/1,125 1,145 1,510/1,490 1,510
EER
11.6 11.6 11.1 11.1 10.8 10.8 9.4 9.4
UNIT WITHOUT
ELECTRIC HEATER
Minimum Circuit Ampacity
2&4
4.0 3.3 4.8 4.1 7.3 5.7 8.4 7.7
CFM
HIGH 220/215 220 220/215 220 290/270 290 325/315 325
LOW 175/155 175 175/155 175 220/190 220 250/220 250
HIGH 235/230 235 235/230 235 310/290 310 345/335 345
LOW 185/165 185 185/165 185 235/205 235 265/235 265
35 35 35 35 45 45 50 50
Dehumidification
(pints/hr)
1.9 1.9 2.7 2.7 3.8 3.8 4.4 4.4
Net Weight
110 110 120 120 130 130 140 140
Shipping Weight (approx.
lbs.)
130 130 140 140 150 150 160 160
Cool, Wet Coil
COOLING DATA (COOLING with ELECTRIC HEAT)
Ventilated Air
Dry Coil
Page view 4