STATUS DISPLAY
ERROR
LIGHT
SUGGESTED ACTION
FP
Freeze
Protection
Engaged. The room temperature
measured by the wireless remote thermostat or indoor
ambient thermistor active sensor falls below 40°F.
YN
No Action required. This setting will disengage
when the room temperature rises above 43°F.
Fd
Front
Desk
switch is closed. All outputs are switched off. Y N
Open front desk switch to allow occupant unit
operation.
Fb
Low Remote Battery Warning. N Y Replace Battery in Wireless Devices.
Indoor Ambient Thermistor reads outside the range -20°F
to 200°F
&
the wireless thermostat is not communicating
to the unit control or
Indoor Ambient Thermistor (IAT) without a wireless remote
thermostat reads outside the range -20°F to 200°F.
F4
Indoor Coil Thermistor either above or below operating
tolerances.
N Y Replace Red Indoor Coil Thremistor .
F5
Wireless Thermostat failure. N Y Replace Wireless Thermostat.
F6
Indoor Discharge Thermistor either above or below
operating tolerances.
NY
Replace Yellow Indoor
Discharge Thermistor.
L6
Discharge Air Too Hot.. N Y Clean Filter or Remove Air Blockage.
L8
Air Restriction in Heating. N Y Clean Filter or Evaporator Coil.
L9
Air Restriction in Cooling. N Y Clean Filter or Evaporator Coil.
LC
Outdoor Coil Thermistor temperature high. N Y
Clean Condensor Coils, Check Fan
fault code. Code will reset after cleaning.
C1
Clean Indoor Coil / Filter. N Y Check for Blocked Indoor Air.
C0
Clean Outdoor Coil. N Y Check for Blocked Outdoor Air.