2
2. CRANKCASE HEATER
Scroll equipped units do not have and do not require a crank-
case heater.
3. TIME DELAY COMPONENT
The time delay is located in the low voltage control circuit.
When the compressor shuts off due to thermostat operation
or a power failure, this components keeps the compressor off
for at least 30 seconds which allows the system pressure to
equalize.
4. UNBRAZING SYSTEM COMPONENTS
If the refrigerant charge is removed from a scroll equipped
unit by bleeding the high side only, it is sometimes possible
for the scrolls to seal, preventing pressure equalization through
the compressor. This may leave the low side shell and suc-
tion line tubing pressurized. If a brazing torch is then applied
to the low side while the low side shell and suction line con-
tains pressure, the pressurized refrigerant and oil mixture
could ignite when it escapes and contacts the brazing flame.
To prevent this occurrence , it is important to check both the
high and low side with manifold gauge before unbrazing, bleed
refrigerant from both the high and low side.
IMPORTANT MESSAGE TO OWNER:
These instructions should be carefully read and kept for
future reference. It is suggested that this booklet be saved for
future references. It is addressed to your dealer and service-
man, but we highly recommend you read it, paying particular
attention to the section titled MAINTENANCE.
The manufacturer assumes no responsibility for equipment
installed in violation of any code or regulation. The manual will
instruct you in the service and care of your unit. Have your
installer go over the manual with you so that you fully under-
stand your air conditioner and how it is intended to function.
The heat pump is a relatively simple device. It operates
exactly as a summer air conditioning unit on the cooling
cycle. Always let the thermostat control system operation. Do
Not try to second guess the thermostat or tamper with it. If the
conditioned area temperature is not suitable, change the
thermostat setting one degree at a time until desired comfort
level is achieved.
A heat pump in the heating mode cannot heat a building as
rapidly as a furnace heats it. It may take a day or two to “pull
down” a cold, moist house when the unit is initially installed
or after prolonged shutdowns.
MAINTENANCE
It is recommended that the outdoor unit be inspected and, if
necessary, cleaned each cooling season. Particular attention
should be given to the air inlet side of the outdoor coil to in-
sure that leaves, grass, etc., are not being drawn into the
unit. Restriction to air flow across the coil will result in loss of
system capacity, high operating pressures and excessive
operating costs. If the outdoor unit is installed adjacent to a
grassy area, it is suggested that lawn mowers be routed in
such a manner that the discharge of the mower will be di-
rected away from the unit. There must be air filters installed
in the system at some point upstream to the indoor coil. Air
filters should be inspected and, if necessary, replaced and/
or cleaned AT LEAST once a month.
If disposable filters are used, an adequate supply of clean,
unused filters of the correct size should be kept available.
Equipment should never be operated without filters.
Permanent type filters may be vacuumed and/or washed but
should not be reinstalled until thoroughly dry. Most air filters
are marked to indicate the direction of air flow, and this should
be carefully noted when they are being installed. Never turn
a dirty filter to allow air flow in the opposite direction.
The blower and motor bearings are permanently lubricated
and do not require additional lubrication.
EQUIPMENT
Some outdoor units have corresponding heaters that are
factory wired in such a manner that they are in operation
whenever the main power supply to the unit is on. Before
starting equipment after prolonged shutdowns or at the
time of initial start up, be sure that the circuits to the units
are closed for at least 24 hours.
APPLICATION
It is not the intent of the manufacturer that this equipment be
used with components other than indicated.
Do not connect to or use any device that is not design-
certified by Goodman for use with this unit. Serious
property damage, personal injury, reduced unit
performance and/or hazardous conditions may result
from the use of such non-approved devices.
Reference Specification Sheets For Performance Val-
ues And Approved System Matches.
LOCATION
The outdoor unit should be located so that air flow through
the coil is unrestricted. To provide adequate service access,
do not locate service side closer than 30.5 cm to any wall or
obstruction.
Consider the affect of outdoor fan noise on conditioned space
and any adjacent occupied space. It is recommended that the
unit be placed so that discharge does not blow toward
windows less than 7.6 m away.
The outdoor unit should be set on a solid, level foundation -
preferably a concrete slab at least 10.2 cm thick. The slab
should be above ground level and surrounded by a graveled
area for good drainage. Any slab used as a unit foundation
should not adjoin the building as it is possible that sound and
vibration may be transmitted to the structure. For rooftop
installation, steel or treated wood beams should be used as
unit support for load distribution.
Comments to this Manuals