1810 Wilson Parkway • Fayetteville, TN 37334
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
ATTENTION INSTALLING PERSONNEL
As a professional installer you have an obligation to
know the product better than the customer. This
includes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize
yourself with this Instruction Manual. Pay special
attention to all safety warnings. Often during
installation or repair it is possible to place yourself
in a position which is more hazardous than when
the unit is in operation.
Remember, it is your responsibility to install the
product safely and to know it well enough to be able
to instruct a customer in its safe use.
Safety is a matter of common sense...a matter of
thinking before acting. Most dealers have a list of
specific good safety practices...follow them.
The precautions listed in this Installation Manual
are intended as supplemental to existing practices.
However, if there is a direct conflict between existing
practices and the content of this manual, the
precautions listed here take precedence.
RCC/RCE
Remote Cooling Condensing Units
Installation Instructions
February 2001
Rev. 1
10652408
Contents
Safety Instructions .............................................................2
General ................................................................................3
SHIPPING AND HANDLING ............................................................ 3
LOCATION AND CLEARANCES ...................................................... 3
ROOFTOP INSTALLATIONS ............................................................ 3
APPLICATION NOTE ........................................................................ 3
Refrigeration Piping ...........................................................4
REFRIGERANT VAPOR AND LIQUID LINE SIZING ...................... 4
REFRIGERANT VAPOR AND LIQUID LINE ROUTING .................. 4
FILTER DRIER INSTALLATION ........................................................ 4
SWEAT CONNECTIONS AT THE UNIT ........................................... 4
Safe Refrigerant Handling..................................................4
LEAK TESTING ................................................................................ 5
ID COIL AND LINE SETS EVACUATION ......................................... 5
Step 1. Confirm Proper Pump And Gauge Operation ............. 5
Step 2. Evacuate Lines And Indoor Coil. ................................. 6
Electrical Connections .......................................................6
System Startup ...................................................................7
FINAL CHARGE ADJUSTMENT ...................................................... 7
Matching System ...................................................................... 7
AMANA-Approved Mix-Matched System Combinations .......... 8
INDOOR COIL WITH EXPANSION VALVE ..................................... 8
INDOOR COIL WITH ORIFICE ........................................................ 8
Troubleshooting .................................................................8
(QUALIFIED SERVICER ONLY) ....................................................... 8
R
RC
®
&Air ConditioningHeating
Built Better Than It Has To B
e
Page view 0
1 2 3 4 5 6 7 8 9 10

Summary of Contents

Page 1 - Installation Instructions

Amana1810 Wilson Parkway • Fayetteville, TN 37334RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.ATTENTION INSTALLING PERSONNELAs a professional installe

Page 2 - Safety Instructions

10System Checklist1 Does the condenser fan blade rotate freely, and is it tight on the shaft?2Does the refrigerant tubing flex freely and not touch an

Page 3 - LOCATION AND CLEARANCES

2Safety InstructionsSafety Guidelines1. Allow only qualified, experienced technicians to install or service thisunit.2. Install the system in accordan

Page 4 - Safe Refrigerant Handling

3GeneralDO NOT locate the unit:—Directly under a vent termination for a gas appliance.—Within 3 feet of a clothes drier vent.—Where water may rise int

Page 5 - LEAK TESTING

4Refrigeration PipingREFRIGERANT VAPOR AND LIQUID LINE SIZINGSee unit “Specification Sheet” for the required vapor andliquid line tubing sizes. The l

Page 6 - Electrical Connections

5WARNINGTo avoid possible explosion:• Never apply flame or steam to a refrigerantcylinder. If you must heat a cylinder forfaster charging, partially

Page 7 - IMPORTANT!

6c. Open the vacuum gauge valve (D) and evacuate to 250microns or less. If the system cannot be evacuated,replace the vacuum pump equipment and repea

Page 8 - Troubleshooting

7correct wire gauge and necessary length of run for properwiring.1. Route the power supply and ground wires through thehigh voltage entrance in the un

Page 9 - OUTDOOR TEMPERATURE

8If pressures and amp draw are too high, remove charge.If you are not using the “Matched Combination” which islisted on the unit "Specification

Page 10 - System Checklist

9450 60 70 80 90 100 110 120681012141618202224262830323436SUPERHEAT @ O.D. UNITOUTDOOR TEMPERATUREDESIRED SUPERHEAT vs OUTDOOR TEMPERATURE90°FIndoor70