RS4200004r7November 2012Service Instructions is a registered trademark of Maytag Corporation or its related companies and is used under license to Goo
10SPECIFICATIONSHEAT PUMP - PTH* Actual vent CFM performance will vary due to application and installation conditions.Notes:¹ All 265-volt models
11SPECIFICATIONSHEAT PUMP - PTH* Actual vent CFM performance will vary due to application and installation conditions.Notes:¹ All 265-volt models
12SPECIFICATIONSHEAT PUMP - PTHPTH G SERIES* Actual vent CFM performance will vary due to application and installation conditions.Notes:¹ All 265-
13SPECIFICATIONSHEAT PUMP HEATING DATANot es: ¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit
14SPECIFICATIONSHEAT PUMP HEATING DATANot es: ¹ All 265-volt model s m ust use an Amana® brand sub- base (PTSB4**E) or an Amana® brand hard-wire k
15PROPER INSTALLATIONOPERATING VOLTAGESWARNINGUSE EXTREME CAUTION WHEN CHECKING HIGH VOLTAGE.Use a voltmeter, check the voltage at the outlet.The read
16PROPER INSTALLATIONWALL SLEEVE INSTALLATIONThe wall sleeve must be installed before the air conditioneror heat pump chassis can be set in place. Rea
17PROPER INSTALLATIONMinimum Interior and Exterior Projectionsin. mm in. mm in. mmWall Sleeve Only 3 75 0 0 0 0Subbase Kit 3 75 3 1/4 85 2 3/4 70Level
18Wall Receptacle Within 58" FromBottom Right Side Corner on208/230 VAC Units OnlyWall Sleeve DimensionsOutside Enclosure Panel RemovalThe sleeve
193. Lift the cabinet front off the chassis. Reverse this pro-cedure to reinstall the cabinet front.CHASSIS INSTALLATION1. Remove the cabinet front fr
2Pride and workmanship go into every product to provide our customers with quality products. It is possible, however,that during its lifetime a produ
20SPECIFICATIONSWIRINGCAUTIONTO AVOID PROPERTY DAMAGE, PERSONAL INJURYOR DEATH DUE TO ELECTRICAL SHOCK:• DO NOT USE AN EXTENSION CORD WITH THIS UNIT.•
21PROPER INSTALLATION18 Pin ConnectorIMPORTANT NOTE: Disconnect power to the unit and/orturn the Master Switch on the control board to OFF whenconnect
22PROPER INSTALLATION3. Wire nut the stripped leads to the two sensor wiresrunning from terminals 2 and 3 on the remote tempera-ture sensor base . 4.P
23WARNINGRemote Control InputsThe C, R, GL, W2, Y/W1, B/O, and GH terminals providecontrol inputs for a “manufacturer-approved” remote wallmounted the
24PROPER INSTALLATIONLocation of 4 Screws4. Rotate the grille 180° end-for-end.5. Reinstall the nuts securing the discharge air grille tothe cabinet f
25Front Mounting Screwaccessedthrough louvers. 3. Remove cabinet front from chassis by tilting the bot-tom of the front forward, lifting slightly up a
26TWO JUMPERSFACTORY DEFAULT“BATTERY”BATTERY CONNECTIONNOTE: For battery connection the 2 jumpers must be posi-tioned as shown above, with jumpers on
27Note: For 24v powered connection, the jumper must beplaced as shown in preceding graphic.DOOR MAGNET INSTALLATIONNOTE: MAGNET BUCKETS ARE SHIPPED FR
28THE SPACE FROM THE TOP OFTHE MAGNET HOLDER AND THE BOTTOMOF THE 01E OR DD01FCANNOT BE MORE THAN 1/8”.The ideal spacing allows a businesscard to be
29CONSTRUCTION STYLE 2Place magnet in Position Bin instances when the doorextends into the roombeyond the door frame.POSITION BCONSTRUCTION STYLE 3Pla
3To locate an authorized servicer, please consult your telephone book or the dealerfrom whom you purchased this product. For further assistance, plea
30PROPER INSTALLATIONDOOR SENSOR OPERATION VERIFICATIONNOTE: Do NOT attempt to bind a DD01E unless properoperation has been validated.To verify that d
31PROPER INSTALLATIONthe HEAT key until appears, then pressthe up and down arrow keys to select ( = appears in the display).For the bedroom u
32PROPER INSTALLATIONpress the up and down arrows to select the last2 digits of the room number.For example for Room “201”, press the HEAT key until
33PROPER INSTALLATIONWARNINGUSE OF SETBACK TEMPERATURESDo not use motion sensing setback temperatures in roomswhere incapacitated persons or animals a
34PROPER INSTALLATIONCONFIGURATION SETTINGSConfiguration Code Description Option Code DescriptionC1 Interface 0* Chassis Membrane*rE Wireless RemoteL5
35MAINTENANCENOTE: The compressor does not require maintenance. Itis hermetically sealed, permanently lubricated.WARNINGWARNINGWARNINGSOME LOCAL CON
36MAINTENANCEVent - (Left Side Unit)Cabinet FrontThe cabinet front and discharge air grille can be cleanedwith a water dampened cloth . Under no circu
37CLEARANCE CHECKClearances around the unit should also be checked to makesure that the intake air and discharge air paths have notbecome blocked or r
38OPERATIONSSEQUENCE OF OPERATIONCooling ModeSet the thermostat to the desired temperature then set themode switch to high or low cool. The fan motor
39OPERATIONS• Indoor/Outdoor Coil Thermistors- In the cooling mode,if the compressor is engaged continuously for 20 min-utes and the Indoor Coil Therm
4PRODUCT IDENTIFICATION PTC 07 3 E 35 A X X X A ABASIC MODEL TYPE MAJOR/MINOR DESIGN REV.PTC = Standard Cooler PTACPTH = Standard
40OPERATIONSDIAGNOSTIC CODESSTATUS DISPLAYERROR LI GHTSUGGESTED ACTIONFPFreeze Protection Engaged. The room temperature measured by the wireless re
41OPERATIONSRefrigeration System - Air ConditionerCondenserCompressorEvaporatorCapillaryTubeProcessStrainerSuction LineDischarge LineCapillaryTubeChec
42OPERATIONSir iRefrigeration Sealed System - Heat Pump (Heat Pump Mode)REFRIGERATION SEALED SYSTEM
43SERVICINGRefer to the cooling and heater performance charts in thissection for capacity test procedure.A step-by-step procedure for determining sour
44SERVICING1. Connect the vacuum pump, vacuum tight manifold setwith high vacuum hoses, thermocouple vacuum gaugeand charging cylinder.2. Connect the
45SERVICINGPlace discharge airthermostat herePlace inlet airthermostat here(Center in grille)Sling PsychrometerThe sling psychrometer is used to obtai
46SERVICINGRead to the right front the 75°F W.B. value in the PTH15column and note the minimum and maximum wattage of1460 - 1575.Since the wattage rea
47SERVICINGPTC073 PTC074 PTC093 PTC094 PTC123 PTC124 PTC153 PTC154Outside CoilDry Bulb (ºF)RoomWet Bulb (ºF)Min Max Min Max Min Max Min Max85132615148
48SERVICINGDIGITAL BOARD DIAGNOSTICSIf a failure is detected on the digital board, there will be agreen light constantly lit up. This light is located
49SERVICINGSTATUS DISPLAYERROR LI GHTSUGGESTED ACTIONFPFreeze Protection Engaged. The room temperature measured by the wireless remote thermostat o
5SPECIFICATIONS* Actual vent CFM performance will vary due to application and installation conditions.Not es:¹ All 265-volt models must use an Ama
50ComplaintPOSSIBLE CAUSEDOTS IN ANALYSISGUIDE INDICATE"POSSIBLE CAUSE"SYMPTOMSystem Will Not StartCompressor will not start - fan runsCompr
51SERVICINGS-1 CHECKING VOLTAGEWARNING1. Using a voltmeter, measure the voltage across termi-nals L1 and L2 of the outlet.2. No reading - indicates op
52SERVICINGChecking OCT Thermistor1. With power off, remove the thermistor leads from thecircuit board.2. Check the thermistor for continuity. See cha
53SERVICINGS-7 DRAIN PAN VALVE (HEAT PUMP MODELSONLY)1. Remove the chassis from the wall sleeve.2. Remove the mounting screw and remove the drain valv
54SERVICINGCapacitorCapacitorCapacitor Capacitor Resistance TESTa. Good Condition - indicator swings to zero and slowlyreturns to infinity. (Start ca
55SERVICINGRemove ScrewsRemoveCoverRemoveScrewsRemoveScrewsFigure D8. Remove the two screws on the left side panel securingthe motor panel assembly, F
56SERVICING1. Remove the motor leads from their respective connec-tion points and capacitor (if applicable).2. Check the continuity between each of th
57SERVICINGa. If the compressor starts and continues run, the causefor failure is somewhere else in the system.b. If the motor fails to start - replac
58SERVICING6. Clean the end of the capillary tube and insert into thetube, it may be necessary to crimp tubing around thecapillary tube, being careful
59SERVICINGFront Mounting Screwaccessedthrough louvers. 2. Grasp the cabinet front as shown.3. Pull the bottom of the cabinet front away from the chas
6SPECIFICATIONS* Actual vent CFM performance will vary due to application and installation conditions.Not es:¹ All 265-volt models must use an Ama
60SERVICINGPOWER CORD1. Remove the unit front by tilting the bottom of the frontoutward and then lift the front straight up.2. Remove the control knob
61SCHEMATICSWARNINGWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.PTC and PTH Standard Mod
62SCHEMATICSWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.WARNINGWiring is subject to cha
63SCHEMATICSWiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.PTC and PTH(Power Door)WARNINGP
64HydronicSCHEMATICSWiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.WARNINGPTC/PTH***E*****
65Hydronic(With Power Vent or Power Door)SCHEMATICSWiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date
66SCHEMATICSWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.WARNINGThe following schematics
67SCHEMATICSWARNINGWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.RDRDRDBLHEATER 2HEATER 1
68SCHEMATICSWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.WARNINGPOWER DOORORPKRDPKBRGYVT
69SCHEMATICSWARNINGWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.HYDRONICLINE 1HEATER 1 H
7SPECIFICATIONS* Actual vent CFM performance will vary due to application and installation conditions.Not es:¹ All 265-volt models must use an Ama
70SCHEMATICSWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.WARNINGPTC/PTH***E******AC; PTC
71SCHEMATICSWARNINGWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.PTC/PTH***E******AC; PTC
72SCHEMATICSWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.WARNINGFOR A HEAT PUMP THERMOST
73SCHEMATICSWARNINGWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.PTH***G*****A* (ID MOTOR
74SCHEMATICSWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.WARNINGPTH***G**[V/D]***A* (ID
75SCHEMATICSWARNINGWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.PTH***G*[H]***A* (ID MOT
76SCHEMATICSWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.WARNINGPTH***G*[H/V]***A* (ID M
77SCHEMATICSWARNINGWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.PTH***G*****A* (ID MOTOR
78SCHEMATICSWARNINGWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.RDRDBLHEATER 2HEATER 1CO
79SCHEMATICSWARNINGWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.ORPKRDPKBRGYVTPKRD8RCOMG
8SPECIFICATIONS* Actual vent CFM performance will vary due to application and installation conditions.Not es:¹ All 265-volt models must use an Ama
80SCHEMATICSWARNINGWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.LINE 1HEATER 1HEATER 2LI
81SCHEMATICSWARNINGWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.LINE 1HEATER 1HEATER 2LI
82SCHEMATICSWARNINGWiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.8RCOMGND230/265TO MOTORV
9SPECIFICATIONS@ 230V @ 208V @ 265V230/208V 2.5 1 8,500 6,800 - - 2,570 / 2,115 11.2 / 10.1 14.0 15 6-15 P230/208V 3.5 1 12,000 9,900 - - 3,570 / 2,93
Comments to this Manuals