Amana GSH13024 Installation Manual Page 7

  • Download
  • Add to my manuals
  • Print
  • Page
    / 16
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 6
7
WIRING
NOTE: All wiring should be made in accordance with the National
Electrical Code.
Consult your local Power Company to determine the availability of
sufficient power to operate the unit. Check the voltage, frequency,
and phase at the power supply to ensure it corresponds to the unit’s
RATED VOLTAGE REQUIREMENT.
In accordance with the N.E.C. or local codes, install a branch cir-
cuit fused disconnect near the unit. Determine wire sizes and
overcurrent protection from the unit nameplate ampacity and in
accordance with the Minimum Filter Size or the N.E.C. The wiring
should never be sized smaller than is recommended by either of
these two sources.
Fuses smaller than that recommended on the rating plate could
result in unnecessary fuse failure or service calls. The use of
protective devices of larger size than indicated could result in ex-
tensive damage to the equipment. The manufacturer bears no
responsibility for damage caused to equipment as result of the
use of larger than is recommended size protective devices.
All units have undergone a run test prior to packaging for ship-
ment. This equipment has been started at minimum rated voltage
and checked for satisfactory operation. Do not attempt to operate
this unit if the voltage is not within the minimum and maximum
voltages shown on nameplate.
All exterior wiring must be within approved weatherproof conduit.
The unit must be permanently grounded in accordance with local
codes, or in absence of local codes, with N.E.C ANSI/ NFPA NO.
70-1984 or latest edition by using ground lug in the control box.
Fuses or HACR type circuit breakers may be used where codes
permit.
G
G
FOR INTERNAL WIRING SEE WIRING LABEL ATTACHED TO UNIT
See
*NOTE
*NOTE:
LOW VOLTAGE CONNECTORS do not apply to heat pumps with
electric heat. LOW VOLTAGE CONNECTORS apply ONLY to GPC units
with electric heat.
IMPORTANT NOTE: Some single phase units are equipped with a
single-pole contactor. Exercise caution when servicing as only one
leg of the power supply is broken with the contractor.
To wire the unit, make the following high and low voltage connec-
tions.
HIGH V OLTAGE W IRING
Single Phase- Two leads should be connected to terminals
L1 & L2 in the electrical control section, using wire sizes
specified in wiring table.
Three Phase- Three leads should be connected to
terminals L1, L2 and L3 in the electrical section, using
wire sizes specified in wiring table.
LOW V OLTAGE W IRING
Air Conditioners- Connect 24V wires from the thermostat
to the corresponding wires in the control box using No. 18
AWG as follows:
LEAD THERMOSTAT
Red R (24V)
Green G (Fan)
Yellow Y (Cool)
White W1 (Heat)*
Brown W2 (Heat)*
Heat Pumps- Connect 24V wires from the thermostat to
the corresponding wires in the control box using No. 18
AWG as follows:
TERMINAL THERMOSTAT
Red R (24V)
Green G (Fan)
Orange O (Rev. Valve)
White W1 (Heat, 2nd)*
Brown W2 (Heat 3rd)*
Yellow Y (Cool)
C (Blue) C (Common)
*Optional field installed heat connections
INTERNAL W IRING
A diagram detailing the internal wiring of this unit is located on the
electrical box cover. If any of the original wire supplied with the ap-
pliance must be replaced, the wire gauge and insulation must be
the same as the original wiring.
Transformer is wired for 230 volts on the 208/230 models. See wir-
ing diagram for 208 volt wiring.
1. For branch circuit wiring (main power supply to unit
disconnect), the minimum wire size for the length of run
can be determined using the circuit ampacity found on the
unit rating plate and the table below. From the unit
disconnect to unit, the smallest wire size allowable may be
used for the ampacity, as the Disconnect must be in sight
of the unit.