SERVICING
WARNING
HIGH VOLTAGE
D
ISCONNECT ALL POWER BEFORE SERVICING OR
INSTALLING THIS UNIT.
MULTIPLE POWER SOURCES MAY
BE PRESENT.
FAILURE TO DO SO MAY CAUSE PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
VOLT / OHM
METER
COLOR
IDENTIFYING
TAB
Testing Auxiliary Limit Control
WARNING
T
O AVOID POSSIBLE FIRE, ONLY RESET THE AUXILIARY LIMIT CONTROL
ONCE.
I
F IT SHOULD OPEN A SECOND TIME, A QUALIFIED SERVICER
MUST DETERMINE WHY THE AUXILIARY LIMIT OPENED BEFORE
RESETTING AGAIN.
S-302 CHECKING FLAME ROLLOUT CONTROL
A temperature activated manual reset control is mounted to
the manifold assembly on 80% furnaces,
ROLLOUT
SWITCH
Flame Rollout Switch Location
(80% Upflow Furnace Shown, Downflow Similar)
The control is designed to open should a flame roll out
occur. An over firing condition or flame impingement on
the heat shield may also cause the control to open. If the
rollout control opens, the air circulation blower will run con-
tinuously.
On single-stage 80% and 90% models, the ignition control
diagnostic light will flash (6) six times indicating a trip of the
rollout switch.
L
INE VOLTAGE NOW PRESENT
WARNING
1. Remove the burner compartment door to gain access
to the rollout switch(es) mounted to burner bracket.
The servicer should reset the ignition control by opening
and closing the thermostat circuit. Then look for the ignitor
glowing which indicates there is power to the ignition con-
trol. Measure the voltage between each side of the rollout
control and ground while the ignition control tries to power
the gas valve.
2. Measure the voltage between each side of the rollout
control and ground during the ignition attempt. Refer to
the following figure.