BLOWER PERFORMANCE SPECIFICATIONS
13
Cooling-Based Continuous Fan
NOTES:
* Motor CFM maximum
** Motor CFM minimum
1. These charts are for furnaces installed at 0' - 4,500'. At higher altitudes, a properly derated unit will have the same temperature rise at a
particular CFM, while the ESP at that CFM will be lower.
2. The installation must be adjusted to obtain a temperature rise within the range listed on the furnace nameplate.
3. Do not operate above .5" w.c. ESP in heating mode.
4. Propane gas installations will have a High Stage rise approximately 4° lower than shown in above table.
Cooling
Speed
Tap
Adjust Tap
CFM @
.1" to .8" W.C.
ESP
Cooling
Speed
Tap
Adjust Tap
CFM @
.1" to .8" W.C.
ESP
Cooling
Speed
Tap
Adjust Tap
CFM @
.1" to .8" W.C.
ESP
Minus (-) Tap 361** Minus (-) Tap 563** Minus (-) Tap 563**
Nominal 361** Nominal 563** Nominal 563**
Plus (+) Tap 370 Plus (+) Tap 563** Plus (+) Tap 563**
Minus (-) Tap 403 Minus (-) Tap 563** Minus (-) Tap 563**
Nominal 448 Nominal 616 Nominal 616
Plus (+) Tap 493 Plus (+) Tap 678 Plus (+) Tap 678
Minus (-) Tap 554 Minus (-) Tap 706 Minus (-) Tap 706
Nominal 616 Nominal 784 Nominal 784
Plus (+) Tap 678 Plus (+) Tap 862 Plus (+) Tap 862
Minus (-) Tap 706 Minus (-) Tap 9*07 Minus (-) Tap 907
Nominal 784 Nominal 1,008 Nominal 1,008
Plus (+) Tap 862 Plus (+) Tap 1,109 Plus (+) Tap 1,109
AA
AMV80704BX** AMV80905CX** AMV81155CX**
A
BBB
CCC
DDD