SERVICING
29
S-16C CHECKING ECM MOTOR WINDINGS
WARNING
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing.
Multiple power sources may be present. Failure to do
so may cause property damage, personal injury
or death.
1. Disconnect the 5-pin and the 16-pin connectors from the
ECM power head.
2. Remove the 2 screws securing the ECM power head and
separate it from the motor.
3. Disconnect the 3-pin motor connector from the power
head and lay it aside.
4. Using an ohmmeter, check the motor windings for conti-
nuity to ground (pins to motor shell). If the ohmmeter
indicates continuity to ground, the motor is defective and
must be replaced.
5. Using an ohmmeter, check the windings for continuity
(pin to pin). If no continuity is indicated, the thermal limit
(over load) device may be open. Allow motor to cool and
retest.
16-pin
connector
5-pin
connector
3-pin motor
connector
S-16D ECM CFM ADJUSTMENTS
MBE MOTOR
This section references the operation characteristics of the
MBE model motor only. The ECM control board is factory set
with the dipswitch #4 in the “ON” position and all other
dipswitches are factory set in the “OFF” position. When MBE
is used with 2-stage cooling units, dipswitch #4 should be in
the "OFF" position.
For most applications, the settings are to be changed
according to the electric heat size and the outdoor unit
selection.
The MBE product uses a General Electric ECM
TM
motor.
This motor provides many features not available on the
traditional PSC motor. These features include:
Improved Efficiency
Constant CFM
Soft Start and Stop
Improved Humidity Control
MOTOR SPEED ADJUSTMENT
Each ECM™ blower motor has been preprogrammed for
operation at 4 distinct airflow levels when operating in
Cooling/Heat Pump mode or Electric Heat mode. These 4
distinct levels may also be adjusted slightly lower or higher
if desired. The adjustment between levels and the trim
adjustments are made by changing the dipswitch(s) either to
an "OFF" or "ON" position.
DIPSWITCH FUNCTIONS
The MBE air handler motor has an electronic control that
contains an eight (8) position dip switch. The function of
these dipswitches are shown in Table 1.
Dipswitch Number Function
1
2
3
N/A
4
Indoor Thermostat
5
6
7
8
Cooling & Heat Pump CFM
CFM Trim Adjust
Electric Heat
Table 1
CFM DELIVERY
Tables 2 and 3 show the CFM output for dipswitch combi-
nations 1-2, and 5-6.
Model Switch 1 Switch 2 CFM
OFF
OFF
1,200
ON
OFF
1,000
OFF
ON
800
ON
ON
600
OFF
OFF
1,600
ON
OFF
1,400
OFF
ON
1,200
ON
ON
1,000
OFF
OFF
2,000
ON
OFF
1,800
OFF
ON
1,600
ON
ON
1,200
OFF
OFF
1,100
ON
OFF
850
OFF
ON
700
OFF
OFF
2,050
ON
OFF
1,750
OFF
ON
1,600
OFF
ON
1,200
AEPT30
AEPT36/60
MBE1200
MBE1600
MBE2000
Electric Heat Operation