Amana PCC**C Installation Manual Page 7

  • Download
  • Add to my manuals
  • Print
  • Page
    / 8
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 6
7
NOTE: If Horizontal Duct Cover kits are required, align the
horizontal duct covers (Figure 9) over the flange brackets
just installed and secure with screws included in the Horizontal
Duct Cover kit.
2
2
Figure 9
Horizontal Duct Cover Alignment
Ductwork
Duct systems and register sizes must be properly designed
for the C.F.M. and external static pressure rating of the unit.
Ductwork should be designed in accordance with the rec-
ommended methods of Air Conditioning Contractors of
America Manual D (Residential) or Manual Q (Commer-
cial). All ductwork exposed to the outdoors must include a
weatherproof barrier and adequate insulation.
A duct system should be installed in accordance with
Standards of the National Board of Fire Underwriters for the
Installation of Air Conditioning, Warm Air Heating and
Ventilating Systems. Pamphlets No. 90A and 90B.
The warm air supply duct from the unit through a wall
fabricated of combustible material may be installed without
clearance. However, minimum clearances for the unit must
be observed as shown in Specification Sheet.
The outlet duct should be provided with an access panel.
For vertical airflow, the ductwork should be attached to the
roof curb prior to installing the unit. Ductwork dimensions
are shown in the Amana PRC roof curb installation manual.
If desired, supply and return duct connections to the unit
may be made with flexible connections to reduce possible
unit operating sound transmission.
Filters
CAUTION
To prevent property damage due to fire and
loss of equipment efficiency or equipment
damage due to dust and lint build up on
internal parts, never operate unit without a
filter installed.
Even though a return air filter is not supplied with this unit,
there must be a means of filtering all return air.
Refer to Specification Sheet provided with unit for filter size
information.
If using the Over/Under Transition Kit, the filter(s) may be
located in the return air duct(s) or return air filter grille(s).
Filters installed external to the unit should be sized in
accordance with their manufacturer recommendations. A
throwaway filter must be sized for a maximum face velocity
of 300 feet per minute.
FILTER INSTALLATION
Important: When installing a filter, the air flow arrows on
the filter must point toward the circulating air blower.
VII. Condensate Drain
CONDENSATE DRAIN CONNECTION
This unit has a built-in trap - no external trap is required; the
drain may be extended using 3/4” PVC piping.
VIII. Normal Sequence of Operations
NOTE: There is a fan delay on initial power to unit before the
low voltage board resets and is operational.
COOLING
1. Thermostat calls for cooling. The compressor and
outdoor fan start.
2. Thirty seconds later, the indoor fan starts and cool air
is delivered to the conditioned space until the thermostat
is satisfied.
3. After the thermostat is satisfied, the compressor and
outdoor fan shut off; 30 seconds later, the indoor fan
shuts off.
NOTE: The extra fan time allows additional cooling from the
indoor coil to be transferred to the conditioned space.
Heating (Electric)
1. Thermostat calls for heating.
2. Thirty seconds later, the indoor fan starts and heat is
delivered to the conditioned space until the thermostat
is satisfied.
3. In another 30 seconds, the indoor fan shuts off.
IX. Startup and Adjustment
CAUTION
This unit must not be used as a
“construction heater” during the finishing
phases of construction on a new structure.
This type of use may result in premature
failure of the unit due to extremely low
return air temperatures and exposure to
very dirty atmospheres.
Page view 6
1 2 3 4 5 6 7 8

Comments to this Manuals

No comments