Troubleshooting information
WARNING
To avoid risk of electrical shock, personal injury, or death, disconnect electrical power source to unit and
discharge capacitor through a 10,000 ohm resistor before attempting to service, unless test procedures require
power to be connected. Ensure all ground wires are connected before certifying unit as repaired and/or
operational.
Possible Causes Corrective Action
Symptom
Insufficient cooling.
Excessive noise.
Low refrigerant charge.
Restricted air flow.
Unit undersized for area/room.
Outside coil fan blade or inside coil
blower wheel loose or improperly aligned.
Compressor mounting hardware loose or
grommets worn.
Free parts, loose screws causing or allowing
excessive vibration.
Worn fan motor bearings.
Test sealed system for proper
charge. Ensure system is free
of leaks.
Inspect air filter, indoor/
outdoor coil for dirt. Clean as
required. Check fins on coils
for damage. Straighten fins if
bent, attempt other repairs as
necessary. Replace coil if
repairs cannot be made.
Reduce area being cooled or
replace unit with larger
capacity model.
Check fan blade!blower wheel
for proper position. Reposition
blade or bower wheel.
Ensure hardware attaching fan
blade/blower wheel to motor
shaft is tight.
Check mounting bolts for
tightness. Tighten if
necessary. Don't overtighten.
Inspect grommets for wear.
Inspect unit for parts that may
have worked free, loose/
missing screws, other
)roblems that
may cause excessive
vibration.
Replace motor
10 16022061 Rev. 0 @2003 MaytagAppliancesCompany